The purpose of this manual is to describe boards
GC600
,
GC600
Mains
.
LOCKOUT
- is used to indicate a fault that prevents the generator from operating and causes automatic
and immediate emergency engine shut-down.
POWER-OFF
- is used to indicate a fault that prevents the generator from operating and causes the
standard automatic engine shutoff (including a cooling phase).
WARNING
- is used to indicate a fault that requires the intervention of the operator without engine
shutoff.
MAINS
– Public power supply line.
LOAD/BUS
– Electrical power supply line of the loads. It can be connected to more gensets
GENERATOR
– Electricity line that is connected to the alternator of the Generator set
LOAD
– Electrical power supply line of the loads. This can be connected to the
Mains
or to the
Generator
MCB
- Switch or component to manage the switching between the
Mains
line and the
Load
line.
GCB
– Switch or component to manage the switching between the
Generator
line and the
Load
line.
CANBUS
- Interface for the control and diagnostics of engines equipped with SAE J1939 or Can Bus
MTU interface.
ISLAND -
Type of plant where one or more gensets supply the
Load
without being in parallel with the
Mains.
MPM
–
Type of plant working in
Island mode
and gensets working in parallel among them.
SSB + SSTP
(Single Stand By + Single Short Time Parallel) - Type of plant where the genset starts and
supplies the
Load
in case of
Mains failure
; once back to normal conditions, it carries out a short time
parallel with the
Mains
, it disconnects from the
Mains
and from Load and it stops in stand-by. Depending
on the configuration of the plant, it is also possible to synchronize the
Genset
with the
Mains
before
disconnecting it in order not to leave the Load without supply.