User manual GC600-GC600
Mains
29
The calendar/time setting is possible in all operating modes: “
OFF/RESET
”, “
MAN
”, “
AUTO
” or “
TEST
”.
To update the time and/or date of the device, enter the
“4.7.1 Date – Time”
menu.
Use the
UP
and
DOWN
buttons to navigate between the sub-menus and the
ACK/ENTER
button to open the sub-menu. The full path to the Date/Time programming page is:
“P.023 PROGRAMMING, 4 AUXILIARY FUNCTIONS, 4.7 Device, 4.7.1 Date-Time”.
Press the
ACK/ENTER
button to view the 6
Date/Time
pages.
Use the
UP
and
DOWN
; navigation buttons to move between the parameters and/or
change their values the
ACK/ENTER
button is used to confirm the value and/or the
Esc/SHIFT
button to cancel the change.
If the values are between
<…>
this means you are not authorised to access and modify the parameters.
See paragraph
4.5.1.1 Access codes
to enable authentication for th
e “
User
” password.
To return to the start menu, press the
Esc/SHIFT
button consecutively.
Gen-set implements the full management of the fuel pump, to pump fuel from the storage tank to the
tank on the generator. The pump can be managed automatically or manually using the controls on the
front panel. Select function
9.1
With
MODE UP
Ref.1a
and
MODE
DOWN
Ref.1a
buttons, select the
MAN, AUTO
or
TEST
mode. With the
UP
and
DOWN
navigation buttons, select the “STATUS (S.xx) Status
information” menu, scroll the pages with the
LEFT
and
RIGHT
navigation buttons to page
S.10 FUEL PUMP
. From here you can use the standard setting procedure by pressing the
ACK/ENTER
button to start (square brackets [xxxxxxx] flashing), and the
UP
and
DOWN
buttons
to modify the command mode:
•
2-AUTOMATIC
(the pump is automatically activated when the low fuel level sensor intervenes
and stops at the fuel maximum level)
•
1-MANUAL-ON
(pump active - the pump is activated when the fuel drops below the maximum
level, and turns off when it exceeds it, keeping the level constant).