16 User manual GC600-GC600
Mains
In this mode, the information on the system status are supplied.
You can scroll through the various pages using the
LEFT
and
RIGHT
buttons.
Page
S.01 (STATUS)
shows system status information. Part of this information are displayed in the
upper title bar if you press and hold the
ESC/SHIFT
button.
The page
S.02 (ANOMALIES)
is automatically displayed in case a new anomaly arises. For every
anomaly, it is shown:
A letter that identify the type.
o
“A”: alarm (block)
o
“U”: Unload.
o
“D”: deactivation.
o
“W”: warning.
A three-digit numeric code that uniquely identify the anomaly. This code flashes if the
anomaly has not been acknowledged yet with
ACK/ENTER
Page
S.03 (BOARD STATUS)
displays the information of the device and contains:
Current date and time in long format (flashing if the clock is not valid)
The univocal series number of the controller (
“Cod. ID”).
The software codes are currently uploaded on the controller.
The necessary internal code to get a temporary SICES level password.
The internal temperature of the controller
The language currently used by the device. It is also possible to select a different language:
press button
ACK/ENTER
, select a language using vertical
UP
and horizontal
DOWN
navigation buttons and confirm with
ACK/ENTER
.
NOTE: GC600 is provided with the only languages ENGLISH, ITALIAN and PORTUGUESE.
With program BoardPrg3 is possible to transfer other languages to the controller.
The page
S.04 (SERIAL COMMUNICATION)
displays the status of the serial communication towards
the two serial ports and by USB. In case of functional problems, please check the content of this
page.
For each serial port (and for the USB too) the status (stand-by, communicating, etc.) and the
counter of the receiving errors are displayed.
If the controller is connected to a modem, it is also displayed:
The modem
’s model.