12
<Note>
Use good quality soft water such as suitable tap water
for the coolant.
Use a long-life coolant (LLC) in order to prevent
freezing and rust. (This generator is filled with coolant
having a 30%-LLC (Besco LLC Super Type E) mixing
ratio when shipped from the factory.)
Use an LLC mixing ratio within a range of 30% to 45%
according to the minimum outdoor air temperature.
Use LLC in the sub tank also.
Approximate LLC Mixing Ratios
Minimum
Temperature
-15°C
-20°C
-30°C
Mixing Ratio
30%
35%
45%
6-3. Fuel Inspection
Check that there is sufficient fuel and add fuel if insufficient.
<Note>
Use JIS No. 2 diesel fuel (-5°C or more).
In cold weather, use JIS No. 3 diesel fuel (-15°C and
above) or JIS Special No. 3 diesel fuel (-25°C and
above).
Be sure to always use the fuel strainer attached to the fuel
filler.
Do not add fuel past the ring.
6-4. Inspection for Fuel/Oil/Cooling Water Leakage
Open the front and rear doors, and check that there are no fuel leaks from fuel pipes and
similar parts, and no oil or coolant leaks.
Open the fuel lever while checking and be sure to always close it after you have completed
the inspection.
Fuel Filter
Net
Sub Tank
Ring
Fuel Strainer
WARNING: FIRE
This generator uses diesel fuel. Be sure to always stop the engine before
checking the fuel or refueling, and absolutely do not allow flame near the
generator when performing such procedures. Wait until the engine cools
before performing such procedures.
If fuel spills, be sure to always wipe it up. Never operate the generator if
there is a fuel leak and always repair the leak before operating again.
WARNING: FIRE
If fuel spills, be sure to always wipe it up. Never operate the generator if
there is a fuel leak and always repair the leak before operating again.