31
<Note>
Do not crank the starter motor for 15 seconds or more continuously.
If repeating starter switch operation, wait 30 seconds or more between operations.
After the engine starts, do not turn the starter switch to "START" during operation.
During operation, the 3-phase output voltage of the power source is constantly
Displayed by the meter voltage display regardless of whether the circuit breaker is set
to
“ON” or “OFF”.
■
Restarting after Stopping due to Running Out of Fuel
The equipment includes an automatic air-bleeding device. You can easily restart the engine
according to the following procedures even if the engine stops due to running out of fuel.
1)
Turn all circuit breakers (3-P, 1-P and circuit protector) to "OFF".
2)
Turn the starter switch to the "STOP" position.
3)
Add fuel to the fuel tank.
4)
Turn the starter switch to the "START" position and crank the starter motor for
approximately 10 seconds.
5)
After the engine starts, remove your hand from the starter switch.
6)
Wait for air to be completely bled from the fuel pipes and engine speed to stabilize (approx.
1-minute). (Engine speed is not stable until all air is bled from the fuel pipes.)
<Note>
Do not apply any loads until all the air has been bled from the fuel pipes (until speed is
stable). Doing so can cause a malfunction.
■
Recovery from Overcurrent Breaker Operation
Caution: Injuries
Always be sure to turn off the power switches of all devices using the generator
when turning on the generator circuit breakers. Leaving on the power switch of a
device using the generator when the generator circuit breakers are turned on
could result in the sudden operation of the corresponding device.
Circuit breakers operate when there is excessive current to isolate the corresponding circuit.
Inspect the circuit breakers if a device being used stops during equipment operation.
Follow the following procedures to recover operation when breakers operate due to
overcurrent.
1)
Turn off all switches of devices using the generator as an AC power source.
2)
Push up the circuit breaker lever that has operated to the "ON" position.
Fuel
valve
Close
Open
Terminal
Cover
(Close)
Ring Latch
(ROCK)
Bolt (M6)
Summary of Contents for DG15BMK
Page 2: ......
Page 11: ...6 LABEL REPRODUCTION X564 000640 X564 000620 X505 000240 X505 006420 X505 006410...
Page 12: ...7 M707 000260 X564 000630 X564 000610 X505 004890 X505 006430 X564 000650...
Page 48: ...43 13 Engine Wiring Diagram...
Page 49: ...44 14 Generator Wiring Diagram...
Page 50: ......
Page 51: ......