30
Caution: Physical and Secondary Damage
If using the equipment as a power source for medical equipment, you must
check with the medical equipment manufacturer, doctor and hospital before
using the equipment.
Caution: Fire
Starting this product in an explosive atmosphere location may cause an
explosion even with the weak sparks generated by the switch of the equipment.
Do not take this equipment into an explosive atmosphere location.
Caution: Electric shock
Do not splash water onto the equipment or operate it in the rain.
Do not connect the AC output to any indoor wiring.
<Note>
Check that the surrounding area is safe before starting the engine.
When there are multiple workers who are working together, they must mutually signal each
other before starting the engine.
Do not use in an area with high temperature or humidity, or an area with a large amount of
dust.
Do not open any doors during operation. Operating with a door open can negatively affect
cooling effect, resulting in an equipment malfunction.
Use ear protection if the level of noise is high. Failure to do so could result in hearing
damage.
9-1. Initial startup / Pre-check
1)
Turn all connected
equipment’s switches to “OFF”
2)
Turn all circuit breakers (3-P, 1-P and circuit protector) to "OFF".
3)
Turn the fuel valve (on the fuel strainer) to "OPEN".
4)
Check the emergency stop switch is released and terminal covers are closed by tighten
bolt.
5)
If the temperature is 5°C or less, turn the starter switch to the "PREHEAT" position and
wait until the preheat lamp turns off. (Approx. 5 seconds)
6)
Turn the starter switch to the "START" position to start the starter motor, which then starts
the engine.
7)
After the engine starts, remove your hand from the starter switch.
8)
Allow the engine to warm up for approximately 5 minutes.
9)
Turn the circuit breakers to
“ON” to start power transmission.
Starter Switch
Preheat Lamp
1-Phase
Breaker
3-Phase
Breaker
1-Phase
Breaker
3-Phase
Leakage Relay
Summary of Contents for DG15BMK
Page 2: ......
Page 11: ...6 LABEL REPRODUCTION X564 000640 X564 000620 X505 000240 X505 006420 X505 006410...
Page 12: ...7 M707 000260 X564 000630 X564 000610 X505 004890 X505 006430 X564 000650...
Page 48: ...43 13 Engine Wiring Diagram...
Page 49: ...44 14 Generator Wiring Diagram...
Page 50: ......
Page 51: ......