Code Meaning
Response
(P)
Sub-
code
Meaning
Possible cause
Measure
111
Internal
"Timeout"
error
Rapid stop/
warning
0
Communication
error with the
power section
Not able to establish a
connection with the
"PFA-..." power sec-
tion (connection
failed).
When using the ap-
plication module
"Transparent 3PD"
•
In MOVITOOLS
®
MotionStudio,
right-click the
device.
•
Choose [Applica-
tion modules] >
[Application Con-
figurator].
•
Choose [Open
configuration from
controller]. Check
the following set-
tings, and adjust
them, if necessary:
– Controller inter-
face = SBUS_1
– Axis address =
20
– Device type
= MOVIPRO LT
When using other
application modules
•
In MOVITOOLS
®
MotionStudio,
right-click the
power section of
your device.
•
Choose [Techno-
logy Ed-
itor] > [Drive start-
up for MOVI‑PLC/
CCU] and start up
the drive.
116
The existing connec-
tion to the "PFA-..."
power section was in-
terrupted.