Code
Meaning
Possible cause
Measure
buS Err
Fieldbus error
•
Check the fieldbus
cabling to the higher-level
controller.
•
Check the fieldbus para-
meterization of the device
and the higher-level con-
troller.
InI
Initialization: A connection is
established with all internal
components.
This can take several
minutes after a device re-
placement.
oFF
The maintenance switch is
switched off.
Switch on the maintenance
switch.
Devices without interface
box:
Check the DC 24 V cabling
and the cabling of the switch
feedback.
OFL
Internal communication error
While backing up data or
restoring a data backup:
Wait a few minutes until the
display changes.
In normal operation:
•
Disconnect the device
from the AC 400 V supply
and the DC 24 V supply
voltage for at least 30 s.
•
Restart the device.
run
The connection has been es-
tablished successfully. The
statuses of the components
or the application are dis-
played after 3 s.
SF1
Communication error with the
power section
•
Parameter channel 2 not
activated (
P889
)
•
Manual operation not fin-
ished
•
Parameter lock power
section activated (
P803
)
•
Configuration in the Ap-
plication Configurator not
completed or not com-
pletely loaded
•
Activate parameter chan-
nel 2
•
Activate and deactivate
manual mode
•
Disconnect the device
from the AC 400 V supply
and the DC 24 V supply
voltage for at least 30 s.
•
Restart the device.