78
Operations
-48 VDC Remote Power Manager
Installation and Operations Manual
To unlock a locked outlet:
At the Switched -48 VDC: prompt, type
set outlet locked
, followed by a locked outlet name, followed by
no
, and
press
Enter
.
Example
The following command unlocks outlet TowerA_InfeedA_Outlet1:
Switched -48 VDC: set outlet locked TowerA_InfeedA_Outlet1 no<Enter>
Displaying outlet information
The Show Outlets command displays information about all outlets. This information includes:
Reboot timer values
Descriptive outlet name, if applicable
Outlet wakeup state
Current outlet locked status
To display outlet information:
At the Switched -48 VDC: prompt, type
show outlets
and press
Enter
.
Example
The following command displays all outlet information:
Switched -48 VDC: show outlets<Enter>
Outlet Outlet Wakeup Locked
ID Name State <No Control>
.A1 DataServer_1 On Yes
.A2 WebServer_1 On Yes
.A3 FileServer_1 On No
.A4 TowerA_Outlet4 On No
.A5 TowerA_Outlet5 On No
.A6 TowerA_Outlet6 On Yes
.A7 TowerA_Outlet7 On No
.A8 TowerA_Outlet8 On No
.A9 TowerA_Outlet9 On No
.A10 TowerA_Outlet10 On No
.A11 TowerA_Outlet11 On No
.A12 TowerA_Outlet12 On No
.A13 TowerA_Outlet13 On No
.A14 TowerA_Outlet14 On No
.A15 TowerA_Outlet15 On No
.A16 TowerA_Outlet16 On No
More (Y/es N/o):
Outlet Options:
Reboot Delay: 15 seconds
Command successful