102
Operations
-48 VDC Remote Power Manager
Installation and Operations Manual
Enabling/disabling UPS voltage polling:
With a UPS record configured, the CDU by default enables voltage polling of the UPS. This feature can be enabled or
disabled using the Set UPS VPoll command.
To enable/ disable UPS voltage polling:
At the Switched -48 VDC: prompt, type
set ups vpoll
and press
Enter
.
At the prompt, enter the index number for the UPS record to be changed and press
Enter
.
At the prompt, type
on
or
off
, and press
Enter
.
Example
The following command disables voltage polling for the record at index number 2:
Switched -48 VDC: set ups vpoll<Enter>
UPS UPS Voltage
Index Type Polling
1 Liebert On
2 MGE On
Select UPS (1-11): 2<Enter>
Voltage Polling: Off<Enter>
Adding an infeed to a UPS:
The Set UPS AddInfeed command adds a logical association of an infeed to a UPS.
To add an infeed to a UPS:
At the Switched -48 VDC: prompt, type
set ups addinfeed
and press
Enter
.
At the prompt, enter the index number for the UPS record to be changed and press
Enter
.
At the prompt, type the absolute infeed ID of the desired infeed, and press
Enter
.
Example
The following command associates infeed .aa to UPS record at index number 1:
Switched -48 VDC: set ups addinfeed<Enter>
UPS UPS Infeed
Index Type IDs
1 APC
2 Liebert .AA
Select UPS (1-11): 1<Enter>
Infeed ID: .aa<Enter>
Removing an infeed from a UPS:
The Set UPS DelInfeed command removes a logical association of an infeed from a UPS.
To remove an infeed from a UPS:
At the Switched -48 VDC: prompt, type
set ups delinfeed
and press
Enter
.
At the prompt, enter the index number for the UPS record to be changed and press
Enter
.
At the prompt, type the absolute infeed ID of the desired infeed, and press
Enter
.
Example
The following command removes the association of infeed .aa from UPS record at index number 2:
Switched -48 VDC: set ups addinfeed<Enter>
UPS UPS Infeed
Index Type IDs
1 APC .AA
2 Liebert .AA
Select UPS (1-11): 2<Enter>
Infeed ID: .aa<Enter>