CABLE INLET
For cable routing, the lower section of the enclosure is equipped with seats for cable clamps PG11 and PG 13.5 to
be punched out when required.
!
Cable routing
CAUTION: Close all inlets securely to prevent the penetration of
insects which may damage the control unit.
WALL-MOUNTING THE CONTROL UNIT
Ø 6 ÷ 8 mm
Position the equipment in the vicinity of the gate, so
that the length of the cables for connection to the rest
of the system are as short as possible.
Secure the control unit with the cable routing holes
facing downwards.
Page 8/18
NO
NO
YES
OPENING AND CLOSING THE BOX
When opening the box, ensure that the hinges protrude
sufficiently from the guide on the base to ensure that the cover
remains open without obstructing control unit wiring operations.
Always accompany the cover when closing until it returns
completely inside the hinges, taking care that the seal is inserted
correctly. Close the cover with the relative screws.
Advice for wiring up in non-specialised environments.
1. Fit an omnipolar switch upstream of the system, choosing one with a gap of at least
3mm between the contacts. Or, alternatively, use a 10A thermal magnetic circuit
breaker switch.
2. Make all types of connection with the system disconnected from the power, i.e. with the
main switch set to OFF (symbol “0”). The control unit, in particular, must never be
connected to the power supply either during the wiring up, or when fitting any expansion
cards.
3. The following cables must be used for installation of the system:
2
- for the control unit, motor and electric lock power supplies: 1.5mm section for lengths
2
of up to 19m, 2.5mm section for lengths of up to 31m,
2
2
- for the flashing light: 0.75mm section for lengths of up to 3m, 1.5mm section for
lengths of up to 19m,
- for the low voltage and current lines, (e.g. for the photocells, control buttons,
2
electromechanical key, sensitive edges and other safety devices: 0.5mm section for
2
lengths of up to 50m, 0.75mm section for lengths of up to 100m.
4. Wire up the earth connection in compliance with legal provisions.