background image

Page 11/18

SETTINGS OF EACH MICROSWITCH

MICROSWITCH

SETTINGS

DESCRIPTION OF OPERATION

OPERATION

- Single leaf logic: only the output indicated with M1 is activated

- Two-leaf logic: both outputs M1 and M2 are activated (M2 leaf 

delayed on opening)

GATE

CONFIGURATION

1

2

3

ON

4

1

2

3

ON

4

1

2

3

ON

4

1

2

3

ON

4

DECELERATION 

SPEED SETTING

1

2

3

ON

4

1

2

3

ON

4

1

2

3

ON

4

1

2

3

ON

4

- High deceleration speed

- Low deceleration speed

- Final closure stroke active: at the end of the closing cycle, full 

power is applied for 2s to the motors to improve electric lock 
closure.

- Final closure stroke not active.

FINAL CLOSURE

 STROKE

- Release stroke activated: the electric lock is activated during a 

brief phase of closure against the stops, and is deactivated shortly 
after start-up of M1.

- Release stroke deactivated: the electric lock is activated shortly 

before start-up of M1, and is deactivated shortly after start-up of 
M1

1

2

3

ON

4

1

2

3

ON

4

1

2

3

ON

4

1

2

3

ON

4

1

2

3

ON

4

1

2

3

ON

4

1

2

3

ON

4

1

2

3

ON

4

ELECTRIC LOCK 

RELEASE STROKE

!

WARNING: Microswitches must only be adjusted when the control unit is disconnected from the 
power supply; any new microswitch settings are applied on subsequent start-up. 
After making new settings on microswitches, we recommend repeating the work time programming 
procedure (see control unit programming).

!

WARNING:
During deceleration, the force is reduced and therefore the speed depends on the characteristics 
of the motor and gate. AN EXCESSIVELY LOW DECELERATION SPEED COULD PREVENT 
SMOOTH LEAF MOVEMENT IF NECESSARY, DISABLE BY MEANS OF DIP2 OF SW2.

SW1

SW2

1

2

3

ON

4

1

2

3

ON

4

1

2

3

ON

4

1

2

3

ON

4

START-UP 

TORQUE

1

2

3

ON

4

1

2

3

ON

4

1

2

3

ON

4

1

2

3

ON

4

DECELERATION 

SETTINGS

- Deceleration deactivated.

- Deceleration activated.

- Start-up torque activated: on start-up motors are powered up at 

the maximum voltage for 2s.

RECOMMENDED ABOVE ALL IN WINTER

- Start-up torque deactivated: on start-up motors are powered up at 

the voltage set by means of the potentiometer.

WARNING: in this case there may be difficulties with start-

up above all if a low force level is set

!

SIN

CE

 1

96

5

K

IT

/3

0

-3

9

F

 I

 E

ATTENTION: The motors MT/30/2 and MT/38/1 arriving against the stop block while slowing 
down are subjected to vibrations – not damaging – but that might cause some noise.
In order to avoid the noise: 
deactivate the slowing down function – dip2 SW2 in ON-, in this case the leaf arrives against 
the stop block at normal speed

!

Summary of Contents for KIT/30 F

Page 1: ...Compatibility Emissions CEI EN61000 6 3 Electromagnetic Compatibility Immunity CEI EN61000 6 Apart from the legislation mentioned above you are also reminded to comply with the following standards dur...

Page 2: ...T 38 1 KIT 30F KIT 39F COMPONENTS OF KIT 4 x 2 x 2 2 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 Motors MT 30 2 KIT 30F MT 38 1 KIT 39F CR 41 Electronic control unit with built in receiver OG 62 2 channel minitra...

Page 3: ...tacts Or alternatively use a 10Athermal magnetic circuit breaker 2 Always make connections of any type with the system disconnected from the power supply i e with the main switch set to OFF symbol 0 T...

Page 4: ...of travel Fig 2 Otherwise install as necessary 3 Ensure that the distance between the gate hinge and post surface marked A in fig 2 is less than 130 mm for an opening angle of 90 less than 110 mm for...

Page 5: ...the gate is reduced due to the dimensions of the motors In this case installation of the motors on the upper section of the gate is recommended IMPORTANT Failure to observe distances B and C specifie...

Page 6: ...in fig 11 Remove the blank out disk on the right marked internally with D for the right leaf and remove the blank out disk on the left marked internally with S for the left leaf In the hole insert th...

Page 7: ...left hand side To invert the cover opening side proceed as follows WARNING This operation must be performed before fixing the enclosure to the wall Insert a slotted screwdriver in the hinge fixture sl...

Page 8: ...e screws Advice for wiring up in non specialised environments 1 Fit an omnipolar switch upstream of the system choosing one with a gap of at least 3mm between the contacts Or alternatively use a 10A t...

Page 9: ...the noise it is possible to add a bridge rectifier as per diagram BUILT IN RECEIVER ANTENNA Input for antenna connection for built in receiver 23 SHEATH 24 ANTENNA GATE OPEN INDICATOR LIGHT 24Vdc outp...

Page 10: ...ng the power supply voltage via the Power potentiometer on the SERAI CR 41 control unit In any event installation must be in full observance with current standards governing power operated gates remem...

Page 11: ...he power supply any new microswitch settings are applied on subsequent start up After making new settings on microswitches we recommend repeating the work time programming procedure see control unit p...

Page 12: ...rmal status Pedestrian button pressed Open Close button pressed Connection between terminals 8 10 OK No jumper between terminals 8 10 Opening photocell obscured presence of obstacle Closing photocell...

Page 13: ...ding of our motors That is why we recommend you check the impact force setting at the start of winter and summer WARNING If one or more parameters are altered programming must be repeated from the beg...

Page 14: ...N When the leaf reaches the closing stop let at least 5 seconds pass and then press key C WORK once Motor M1 is shut down and the control unit automatically exits the programming phase and is ready fo...

Page 15: ...e right hand button 1 OG 02 or OG 04 microswitch operated mini transmitter as pedestrian control there is no need to store the other OG 02 and OG 04 transmitters simply set the microswitches in the sa...

Page 16: ...optional addition of the SOG 2A expansion bo ard which takes the number of mini transmitters up to 794 After fitting the SOG 4A receiver all the codes stored in the built in receiver must be erased a...

Page 17: ...emperature 10 60 C Dimensions 70 x 40 x 90 mm Weight 120 g RX RX THE CONTACT POSITION REFERS TO WHEN THE RECEIVER IS ENERGIZED 40 mm POSITION DIMENSIONS INSTALLATION RX SPHERICAL ORANGE LAMP WITH BUIL...

Page 18: ...dip2 SW2 set to ON KIT 30 39F I E 10 18 110607 A4Vf r IS KIT30F IS E The remote control range is reduced Unsuitable antenna connection Check that the antenna is connected correctly to terminals 23 and...

Reviews: