INSTALLATION AND OPERATION INSTRUCTIONS — FENCE PROTECTION SYSTEMS
4
Run the sensor cable from each FPS-3 dual zone pre-amp as shown in Figures 2 and 3.
NOTE:
Your installation may utilize either standard "black" sensor cable or Helisensor.
Observe special requirements for each type sensor.
•
Attach the sensor cable to the
fence at approximate 12-inch
intervals with black UV cable ties
as shown in Figure 3. Use ONLY
the approved black UV-protected
cable ties.
•
Provide service loops every 50 feet
and increased sensitivity loops at
each corner or end post. Provide
cable overlap at adjacent zones.
Install TSK termination boxes at
each sensor end-of-line (single-run
cable) and splices if necessary.
•
Connect each sensor cable to the
Pre-Amp as shown in Figure 4.
•
Connect the control wiring to each
dual zone pre-amp as shown in
Figure 4.
Figure 3. Cable Tie Installation
Figure 4. Pre-Amp Cable Connections
Approx. 12"
REMOVABLE
TERMINAL BLOCKS
DUAL ZONE PRE-AMP.
CIRCUIT BOARD
1 2
CENTER
SHIELD
1 2
1 2
CENTER
SHIELD
1 2
SHIELD
ZN 1-1
ZN 1-2
ZN 2-1
ZN 2-2
SEE WIRING
DETAIL
WIRING TO
CENTRAL CONTROLLER
SHIELD
ZN 1-1
ZN 1-2
ZN 2-1
ZN 2-2
RED
BLK
SHIELD
GRN
WHT
TO
CENTRAL
CONTROLLER
NOTE: WIRING COLORS SHOWN MATCH THE
Magal-Senstar
CABLE
LEFT ZONE
SENSOR CABLE
RIGHT ZONE
SENSOR CABLE
Lightly shaded cables
indicate return sensor
cable terminations in a
double run installation
1 MEG
1 MEG