9.5.
Run Time Parameters
Run time parameters feature allows accessing some
TB
OX
LT2
configurations through Tags, in order to
modify them "on line".
For instance, to change a tel. number of a SMS recipient, the e-mail address of a recipient, the address of
SMTP server, the handling of alarm condition, …
When a configuration provides access to run time parameters, a tab is attached to the configuration.
Example with Alarm Recipient:
You associate a Tag to the run time parameter you
want to add
The Tag, and therefore its associated parameter,
can then be modified from TWinSoft, a WebForm,
a SCADA, ...
The format of the Tag depends on the parameter (Bool, Byte, Word, Float, Text)
Changing of parameters is maintained in case of power cycle, reset, reboot and watchdog.
Original configuration is restored in case of sending new program or OS and doing stop/start from
TWinSoft.
9.5.1.
Modbus Device
Parameter
Tag Format
Station Address
URL
Port TCP
Byte
Text
Word
9.5.2.
Alarm Parameters
Alarm Condition
Parameter
Choice
Tag Format
Handling
0 = enabled
1 = disabled
2 = power fail
3 = DisAla
4 = DisAla2
5 = DisAla3
6 = DisAla4
Byte
Threshold (analog)
Byte or Word or DWord or Float
Hysteresis (analog)
Byte or Word or DWord or Float
Summary of Contents for TBOX LT2-530 Series
Page 1: ...User s Guide Cabling Technical Specifications Version 1 09 LT2...
Page 10: ...Version 1 09 10...
Page 11: ...Version 1 09 11...
Page 17: ...Version 1 09 17...
Page 20: ...Version 1 09 20...
Page 21: ...Version 1 09 21...
Page 38: ...Version 1 09 38...
Page 39: ...Version 1 09 39...
Page 151: ...Version 1 09 151...
Page 175: ...Version 1 09 175...