Version : 1.09
163
19.7.
I/O
Group 1 – Internal I/O
DI:
Power Failure
Digital Input returning a failure of Power at Vin, when
TB
OX
LT2
is equipped
with an external 12V Backup battery.
AI:
Power Supply Voltage
Voltage at Vin connection
AI: External 12 V Backup Bat. V.
Voltage at Vbat connection
AI:
Internal Temperature
Temperature inside the
TB
OX
LT2
DI:
STOP Button
Input corresponding to the toggle switch in STOP position. To use STOP action,
go to the TWinSoft application, RTU properties -> Advanced -> Start/Stop
Group 2 - Digital Inputs
Group 6 - Counter
V+
V+ MUST BE POWERED
External voltage to V+ accepted
With cabling only to DI: 8 → 30 VDC
With cabling to DI and DO: 11 → 30 VDC
Voltage at input
Typical
12 VDC
Maximum for a LOW level
2.0 VDC
Minimum for a HIGH level
7.4 VDC
Maximum
30 VDC
Resistance at input
Resistance
> 39 kΩ
Sampling
Minimum period LOW – HIGH
15 msec – 15 msec.
Frequency (software)
At each cycle of BASIC / Ladder
Protection
RC filter
TBD
Voltage inversion
No protection
Protection EMC
RC
Isolation
Between inputs
No isolation
To the power supply
No isolation
Counter inputs
Input channels
DI 0, DI 1, DI 2
Maximum frequency
10 kHz with duty cycle 45 .. 55 %
In all cases, V+ MUST be connected to prevent permanent damage; even when using the
channels as input.
Summary of Contents for TBOX LT2-530 Series
Page 1: ...User s Guide Cabling Technical Specifications Version 1 09 LT2...
Page 10: ...Version 1 09 10...
Page 11: ...Version 1 09 11...
Page 17: ...Version 1 09 17...
Page 20: ...Version 1 09 20...
Page 21: ...Version 1 09 21...
Page 38: ...Version 1 09 38...
Page 39: ...Version 1 09 39...
Page 151: ...Version 1 09 151...
Page 175: ...Version 1 09 175...