Version : 1.09
193
Appendix H. Precautions In Cabling
H.1. Cabling to Spring-Cage Terminal Blocks
TB
OX
LT2
is equipped with compact spring-cage terminal blocks.
This connector allows a high density of connections.
Press the orange plastic with a screwdriver for inserting
and removing the cable.
It is recommended to use either solid cable or stranded cable with ferrule.
Connection capacity
Without ferrule
Solid cable: 0.2 .. 1.5 mm² (24..16 AWG)
With ferrule without plastic sleeve
Solid or Stranded cable: 0.2 .. 1.5 mm²
With ferrule with plastic sleeve
Solid or Stranded cable: 0.2 .. 0.75 mm²
Ferrule specification for 0.75mm² cable
B: minimum 10 mm
C: 1.5 mm
D: 3.5 mm
H.2. Cabling Analog Inputs
One must be particularly careful when cabling temperature probes (Pt1000) and more precisely when
combining temperature probes and 4..20mA sensors.
It is mandatory to cable temperature probes to one of the GND from the AI stage, and to reserve it
uniquely to the probes.
If you mix temperature probes and 4..20mA sensors, use a separate GND for each type of signal.
Example with LT2-542-x
Gnd
Gnd
1
0
Pt1000
5
3
1
0
2
4
4..20mA
4..20mA
4..20mA
+
-