I>>> . tChar
[Protection Para / I>>>]
0.1
0.05 . . . 10.00
P.1
Time multiplier/tripping characteristic factor. The setting range depends on the selected tripping curve.
I>>> . tMin
[Protection Para / I>>>]
0.00s
0.00s . . . 20.00s
P.1
Minimum trip delay time. Independent of the measured current values, the trip delay time does never fall below the
minimum that is set here.
I>>> . Reset Mode
[Protection Para / I>>>]
instantaneous
instantaneous, definite time, inverse time
P.1
Reset Mode
I>>> . tReset
[Protection Para / I>>>]
0.1s
Only available if:
• I>>> . Reset Mode = definite time
•
0.00s . . . 60.00s
P.1
Reset delay for intermittent phase failures (INV characteristics only)
I>>> . IH2 Blo
[Protection Para / I>>>]
Active
Inactive, Active
P.1
Blocking the trip command, if an inrush is detected.
I>>> . ExBlo
[Protection Para / I>>>]
“-”
“-” . . . Prot . Pos OFF
P.1
External blocking of the module if the state of the assigned signal is true.
7.9.3
I>>>: Input States
I>>> . ExBlo-I
[Operation / Status Display / I>>>]
Module input state: External blocking
44
WIC1
WIC1-1.0-EN-REF
7 Protection Parameter
7.9.3 I>>>: Input States