7.19
CBF – Circuit breaker failure protection module
7.19.1
CBF: Device Planning Parameters
CBF . Mode
[Device planning / Projected Elements]
“-”
“-”, use
P.1
Module Circuit Breaker Failure protection, general operation mode
7.19.2
CBF: Settings
CBF . Function
[Protection Para / CBF]
Active
Inactive, Active
P.1
Permanent activation or deactivation of module/stage.
CBF . t-CBF
[Protection Para / CBF]
0.20s
0.00s . . . 1.00s
P.1
If the delay time is expired, a CBF alarm is issued.
CBF . ExBlo
[Protection Para / CBF]
“-”
“-” . . . Prot . Pos OFF
P.1
External blocking of the module if the state of the assigned signal is true.
7.19.3
CBF: Input States
CBF . ExBlo-I
[Operation / Status Display / CBF]
Module input state: External blocking
7.19.4
CBF: Signals (Output States)
CBF . Active
[Operation / Status Display / All Actives]
[Operation / Status Display / CBF]
Signal: active