I2> . Reset Mode
[Protection Para / I2>]
instantaneous
If: I2> . Char = DEFT
• instantaneous, definite time
•
If: I2> . Char = IEC NINV
• instantaneous, definite time, inverse time
•
If: I2> . Char = IEC VINV
• instantaneous, definite time, inverse time
•
If: I2> . Char = IEC EINV
• instantaneous, definite time, inverse time
•
If: I2> . Char = IEC LINV
• instantaneous, definite time, inverse time
•
If: I2> . Char = RINV
• instantaneous, definite time, inverse time
•
If: I2> . Char = HV Fuse
• instantaneous, definite time
•
If: I2> . Char = FR Fuse
• instantaneous, definite time
•
If: I2> . Char = IEEE MINV
• instantaneous, definite time, inverse time
•
If: I2> . Char = IEEE VINV
• instantaneous, definite time, inverse time
•
If: I2> . Char = IEEE EINV
• instantaneous, definite time, inverse time
•
If: I2> . Char = EF Curve
• instantaneous, definite time
•
P.1
Reset Mode
I2> . tReset
[Protection Para / I2>]
0.1s
Only available if:
• I2> . Reset Mode = definite time
•
0.00s . . . 60.00s
P.1
Reset delay for intermittent phase failures (INV characteristics only)
I2> . IH2 Blo
[Protection Para / I2>]
Active
Inactive, Active
P.1
Blocking the trip command, if an inrush is detected.
57
WIC1
WIC1-1.0-EN-REF
7 Protection Parameter
7.13.2 I2>: Settings