I>> – Phase Overcurrent Stage
7.8.1
I>>: Device Planning Parameters
I>> . Mode
[Device planning / Projected Elements]
use
“-”, use
P.1
Phase Overcurrent Stage, general operation mode
I>> . Definition
[Device planning / Definition]
Trip
Trip, Alarm
P.1
Phase Overcurrent Stage: If set to “Alarm”: The function operates as a supervision function, i.e. a fault generates
neither alarm nor trip, but an »Alarm« signal gets issued instead. If set to “Trip”: The function operates as a
protection function, i.e. trips the breaker in case of a fault.
7.8.2
I>>: Settings
I>> . Function
[Protection Para / I>>]
Active
Inactive, Active
P.1
Permanent activation or deactivation of module/stage.
I>> . I
[Protection Para / I>>]
1.00In
0.35In . . . 20.00In
P.1
If the pickup value is exceeded, the protection stage starts to time out to trip.
WARNING: Check the Technical Data and ensure that the actual overcurrent settings for this pickup threshold and the
trip delay comply with the technical limits of the phase current inputs! (The device allows for overcurrent settings
that are out of the permitted range of current values.)
I>> . Char
[Protection Para / I>>]
DEFT
DEFT . . . EF Curve
P.1
Characteristic
I>> . t
[Protection Para / I>>]
0.1s
0.00s . . . 300.00s
P.1
Time delay for trip or alarm
39
WIC1
WIC1-1.0-EN-REF
7 Protection Parameter
7.8 I>> – Phase Overcurrent Stage