7.6
IH2 – Module Inrush
7.6.1
IH2: Device Planning Parameters
IH2 . Mode
[Device planning / Projected Elements]
use
“-”, use
P.1
Module Inrush, general operation mode
7.6.2
IH2: Settings
IH2 . Function
[Protection Para / IH2]
Active
Inactive, Active
P.1
Permanent activation or deactivation of module/stage.
IH2 . IH2 / IH1
[Protection Para / IH2]
20%
15% . . . 40%
P.1
Maximum permissible percentage of the 2nd harmonic of the 1st harmonic.
IH2 . Imax
[Protection Para / IH2]
6.00In
1.0In . . . 20.0In
P.1
Inrush limit value: If the phase current is above this value the inrush blocking is cancelled.
IH2 . tmax
[Protection Para / IH2]
0.3s
0.1s . . . 999.99s
P.1
Maximum duration (phase-selective) of an inrush blocking
IH2 . 3-ph Blo
[Protection Para / IH2]
Inactive
Inactive, Active
P.1
Activation of 3-phase inrush blocking: If an inrush is detected in (at least) one phase all three phases get blocked. (If
this is inactive then only the Inrush-affected phase gets blocked.)
33
WIC1
WIC1-1.0-EN-REF
7 Protection Parameter
7.6 IH2 – Module Inrush