CT Type
Description
Relative
Phase current values are displayed as relative values.
WE2 : 16 A ... 56 A
Phase current values are displayed as primary values, that are calculated based on the
connected CT type with primary current range 16 A ... 56 A.
W2 : 16 A ... 56 A
Phase current values are displayed as primary values, that are calculated based on the
connected CT type with primary current range 16 A ... 56 A.
W3 : 32 A ... 112 A
Phase current values are displayed as primary values, that are calculated based on the
connected CT type with primary current range 32 A ... 112 A.
W4 : 64 A ... 224 A
Phase current values are displayed as primary values, that are calculated based on the
connected CT type with primary current range 64 A ... 224 A.
W5 : 128 A ... 448 A
Phase current values are displayed as primary values, that are calculated based on the
connected CT type with primary current range 128 A ... 448 A.
W6 : 256 A ... 896 A
Phase current values are displayed as primary values, that are calculated based on the
connected CT type with primary current range 256 A ... 896 A.
Polarity
Selection list referenced by the following parameters:
•
•
•
•
Polarity
Description
0
0
180
180 degree polarity correction (wiring faults)
Meth.Detect.Bkr.Pos.
Select the method to be used to determine the connected breaker position.
Selection list referenced by the following parameters:
•
╚═▷ Prot . Meth.Detect.Bkr.Pos.
•
Meth.Detect.Bkr.Pos.
Description
Current-Based
The breaker position is determined based on current measurement.
Aux-Based
The breaker position is dependent on a particular input signal (Aux contacts 52a/52b of
the circuit breaker).
Current and Aux
The breaker position is determined based on current measurement AND input signal
(Aux contacts 52a/52b of the circuit breaker).
94
WIC1
WIC1-1.0-EN-REF
11 Selection Lists