G-4
Setting SEL
OGIC
®
Control Equations
Date Code 20001006
SEL-351 Instruction Manual
SEL
OGIC
Control Equation Parentheses Operator ( )
More than one set of parentheses ( ) can be used in a SEL
OGIC
Control Equation setting. For
example, the following SEL
OGIC
Control Equation setting has two sets of parentheses:
SV7 = (SV7+IN1)*(50P1+50N1)
In the above example, the logic within the parentheses is processed first and then the two
parentheses resultants are ANDed together. The above example is from Figure 7.27 in
Section 7:
Inputs, Outputs, Timers, and Other Control Logic
. Parentheses cannot be “nested” (parentheses
within parentheses) in a SEL
OGIC
Control Equation setting.
SEL
OGIC
Control Equation NOT Operator !
The NOT operator ! is applied to a single Relay Word bit and also to multiple elements (within
parentheses). Following are examples of both.
Example of NOT Operator ! Applied to Single Element
The internal circuit breaker status logic in the SEL-351 Relay operates on 52a circuit breaker
auxiliary contact logic. The SEL
OGIC
Control Equation circuit breaker status setting is labeled
52A. See
Optoisolated Inputs
in
Section 7: Inputs, Outputs, Timers, and Other Control Logic
and
Close Logic
in
Section 6: Close and Reclose Logic
for more information on SEL
OGIC
Control Equation circuit breaker status setting 52A.
When a circuit breaker is closed, the 52a circuit breaker auxiliary contact is closed. When a
circuit breaker is open, the 52a contact is open.
The opposite is true for a 52b circuit breaker auxiliary contact. When a circuit breaker is closed,
the 52b circuit breaker auxiliary contact is open. When the circuit breaker is open, the 52b contact
is closed.
If a 52a contact is connected to optoisolated input IN1, the SEL
OGIC
Control Equation circuit
breaker status setting 52A is set:
52A = IN1
Conversely, if a 52b contact is connected to optoisolated input IN1, the SEL
OGIC
Control Equation
circuit breaker status setting 52A is set:
52A = !IN1
[=NOT(IN1)]
With a 52b contact connected, if the circuit breaker is closed, the 52b contact is open and input
IN1 is deenergized [IN1 = 0 (logical 0)]:
52A = !IN1 = NOT(IN1) = NOT(0) = 1
Thus, the SEL
OGIC
Control Equation circuit breaker status setting 52A sees a closed circuit
breaker.
Summary of Contents for SEL-351
Page 14: ...Courtesy of NationalSwitchgear com ...
Page 16: ...Courtesy of NationalSwitchgear com ...
Page 40: ...Courtesy of NationalSwitchgear com ...
Page 74: ...Courtesy of NationalSwitchgear com ...
Page 146: ...Courtesy of NationalSwitchgear com ...
Page 186: ...Courtesy of NationalSwitchgear com ...
Page 220: ...Courtesy of NationalSwitchgear com ...
Page 304: ...Courtesy of NationalSwitchgear com ...
Page 340: ...Courtesy of NationalSwitchgear com ...
Page 380: ...Courtesy of NationalSwitchgear com ...
Page 450: ...Courtesy of NationalSwitchgear com ...
Page 506: ...Courtesy of NationalSwitchgear com ...
Page 528: ...Courtesy of NationalSwitchgear com ...
Page 534: ...Courtesy of NationalSwitchgear com ...
Page 536: ...Courtesy of NationalSwitchgear com ...
Page 550: ...Courtesy of NationalSwitchgear com ...
Page 562: ...Courtesy of NationalSwitchgear com ...
Page 570: ...Courtesy of NationalSwitchgear com ...
Page 584: ...Courtesy of NationalSwitchgear com ...
Page 602: ...Courtesy of NationalSwitchgear com ...