S
ETTINGS
S
HEET
Page
9
of 24
F
OR THE
SEL-351 R
ELAY
Date
R
ELAY
S
ETTINGS
(S
ERIAL
P
ORT
C
OMMAND
SET
AND
F
RONT
P
ANEL
)
Date Code 20001006
(Make the following settings if preceding enable setting EVOLT = Y and the voltage inputs are delta-
connected)
Phase-to-phase undervoltage pickup (OFF, 0.0 - 260.0 V secondary)
27PP1P =
Phase-to-phase undervoltage pickup (OFF, 0.0 - 260.0 V secondary)
27PP2P =
Phase-to-phase overvoltage pickup (OFF, 0.0 - 260.0 V secondary)
59PP1P =
Phase-to-phase overvoltage pickup (OFF, 0.0 - 260.0 V secondary)
59PP2P =
Negative-Sequence (V2) overvoltage pickup (OFF, 0.0 - 100.0 V secondary)
59Q1P =
Negative-Sequence (V2) overvoltage pickup (OFF, 0.0 - 100.0 V secondary)
59Q2P =
Positive-Sequence (V1) overvoltage pickup (OFF, 0.0 - 150.0 V secondary)
59V1P =
Channel VS undervoltage pickup (OFF, 0.0 - 260.0 V secondary)
27SP =
Channel VS overvoltage pickup (OFF, 0.0 - 260.0 V secondary)
59S1P =
Channel VS overvoltage pickup (OFF, 0.0 - 260.0 V secondary)
59S2P =
Synchronism Check Elements (See Figures 3.26 and 3.27)
(Make the following settings if preceding enable setting E25 = Y)
Voltage window - low threshold
(0.00 - 150.00 V secondary, 150 V wye-connected voltage inputs;
0.00 - 300.00 V secondary, 300 V wye-connected voltage inputs;
0.00 - 260.00 V secondary, delta-connected voltage inputs)
25VLO =
Voltage window - high threshold
(0.00 - 150.00 V secondary, 150 V wye-connected voltage inputs;
0.00 - 300.00 V secondary, 300 V wye-connected voltage inputs;
0.00 - 260.00 V secondary, delta-connected voltage inputs)
25VHI =
Maximum slip frequency (0.005 - 0.500 Hz)
25SF =
Maximum angle 1 (0.00
°
- 80.00
°
)
25ANG1 =
Maximum angle 2 (0.00
°
- 80.00
°
)
25ANG2 =
Synchronizing phase (Wye-connected voltage inputs: VA, VB, VC, or
0
°
- 330
°
in 30
°
steps; degree option is for VS not in phase with VA, VB, or
VC – set with respect to VS constantly lagging VA)
(Delta-connected voltage inputs: VAB, VBC, VCA, or 0 - 330° in 30° steps;
degree option is for VS not in phase with VAB, VBC, or VCA – set with
repsect to VS constantly lagging VAB.)
SYNCP =
Breaker close time for angle compensation
(0.00 - 60.00 cycles in 0.25-cycle steps)
TCLOSD =
Frequency Element (See Figures 3.29 and 3.30)
(Make the following settings if preceding enable setting E81 = 1 - 6)
Phase undervoltage block
(12.50 - 150.00 V secondary, 150 V wye-connected voltage inputs;
25.00 - 300.00 V secondary, 300 V wye-connected voltage inputs;
34.00 - 260.00 V secondary, delta-connected voltage inputs)
27B81P =
Level 1 pickup (OFF, 40.10 - 65.00 Hz)
81D1P =
Level 1 time delay (2.00 - 16000.00 cycles in 0.25-cycle steps)
81D1D =
Summary of Contents for SEL-351
Page 14: ...Courtesy of NationalSwitchgear com ...
Page 16: ...Courtesy of NationalSwitchgear com ...
Page 40: ...Courtesy of NationalSwitchgear com ...
Page 74: ...Courtesy of NationalSwitchgear com ...
Page 146: ...Courtesy of NationalSwitchgear com ...
Page 186: ...Courtesy of NationalSwitchgear com ...
Page 220: ...Courtesy of NationalSwitchgear com ...
Page 304: ...Courtesy of NationalSwitchgear com ...
Page 340: ...Courtesy of NationalSwitchgear com ...
Page 380: ...Courtesy of NationalSwitchgear com ...
Page 450: ...Courtesy of NationalSwitchgear com ...
Page 506: ...Courtesy of NationalSwitchgear com ...
Page 528: ...Courtesy of NationalSwitchgear com ...
Page 534: ...Courtesy of NationalSwitchgear com ...
Page 536: ...Courtesy of NationalSwitchgear com ...
Page 550: ...Courtesy of NationalSwitchgear com ...
Page 562: ...Courtesy of NationalSwitchgear com ...
Page 570: ...Courtesy of NationalSwitchgear com ...
Page 584: ...Courtesy of NationalSwitchgear com ...
Page 602: ...Courtesy of NationalSwitchgear com ...