7-22
Inputs, Outputs, Timers, and Other Control Logic
Date Code 20001006
SEL-351 Instruction Manual
Operation of SEL
OGIC
Control Equation Settings SS1 Through SS6
Each setting group has its own set of SEL
OGIC
Control Equation settings SS1 through SS6.
Table 7.4: Definitions for Active Setting Group Switching
SEL
OGIC
Control Equation Settings SS1 Through SS6
Setting
Definition
SS1
go to (or remain in) setting Group 1
SS2
go to (or remain in) setting Group 2
SS3
go to (or remain in) setting Group 3
SS4
go to (or remain in) setting Group 4
SS5
go to (or remain in) setting Group 5
SS6
go to (or remain in) setting Group 6
The operation of these settings is explained with the following example:
Assume the active setting group starts out as setting Group 3. Corresponding Relay Word bit SG3
is asserted to logical 1 as an indication that setting Group 3 is the active setting group (see
Table 7.3).
With setting Group 3 as the active setting group, setting SS3 has priority. If setting SS3 is
asserted to logical 1, setting Group 3 remains the active setting group, regardless of the activity of
settings SS1, SS2, SS4, SS5, and SS6. With settings SS1 through SS6 all deasserted to logical 0,
setting Group 3 still remains the active setting group.
With setting Group 3 as the active setting group, if setting SS3 is deasserted to logical 0 and one of
the other settings (e.g., setting SS5) asserts to logical 1, the relay switches from setting Group 3 as
the active setting group to another setting group (e.g., setting Group 5) as the active setting group,
after qualifying time setting TGR:
TGR
Group Change Delay Setting
(settable from 0.00 to 16000.00 cycles)
In this example, TGR qualifies the assertion of setting SS5 before it can change the active setting
group.
Operation of Serial Port GROUP Command and Front-Panel GROUP Pushbutton
SEL
OGIC
Control Equation settings SS1 through SS6 have priority over the serial port GROUP
command and the front-panel GROUP pushbutton in selecting the active setting group. If any one
of SS1 through SS6 asserts to logical 1, neither the serial port GROUP command nor the front-
panel GROUP pushbutton can be used to switch the active setting group. But if SS1 through SS6
all deassert to logical 0, the serial port GROUP command or the front-panel GROUP pushbutton
can be used to switch the active setting group.
Summary of Contents for SEL-351
Page 14: ...Courtesy of NationalSwitchgear com ...
Page 16: ...Courtesy of NationalSwitchgear com ...
Page 40: ...Courtesy of NationalSwitchgear com ...
Page 74: ...Courtesy of NationalSwitchgear com ...
Page 146: ...Courtesy of NationalSwitchgear com ...
Page 186: ...Courtesy of NationalSwitchgear com ...
Page 220: ...Courtesy of NationalSwitchgear com ...
Page 304: ...Courtesy of NationalSwitchgear com ...
Page 340: ...Courtesy of NationalSwitchgear com ...
Page 380: ...Courtesy of NationalSwitchgear com ...
Page 450: ...Courtesy of NationalSwitchgear com ...
Page 506: ...Courtesy of NationalSwitchgear com ...
Page 528: ...Courtesy of NationalSwitchgear com ...
Page 534: ...Courtesy of NationalSwitchgear com ...
Page 536: ...Courtesy of NationalSwitchgear com ...
Page 550: ...Courtesy of NationalSwitchgear com ...
Page 562: ...Courtesy of NationalSwitchgear com ...
Page 570: ...Courtesy of NationalSwitchgear com ...
Page 584: ...Courtesy of NationalSwitchgear com ...
Page 602: ...Courtesy of NationalSwitchgear com ...