2-16
Installation
Date Code 20001006
SEL-351 Instruction Manual
IRIG
-
B Time-Code Input
The SEL
-
351 Relay accepts a demodulated IRIG
-
B time signal to synchronize the relay internal
clock with some external source. The demodulated IRIG
-
B time signal can come via the
SEL
-
2020 or SEL-2030 Communications Processors, or the SEL-2100 Protection Logic Processor
listed in Table 2.1.
A demodulated IRIG-B time code can be input into Serial Port 2 on any of the SEL-351 Relay
models (see Table 10.2). This is handled adeptly by connecting Serial Port 2 of the SEL-351
Relay to an SEL-2020, SEL-2030, or SEL-2100 with Cable C273A.
A demodulated IRIG-B time code can be input into the connector for Serial Port 1 on models
0351x0, 0351x1, and 0351xY (see Table 10.3). If demodulated IRIG-B time code is input into
this connector, it should not be input into Serial Port 2 and vice versa.
Summary of Contents for SEL-351
Page 14: ...Courtesy of NationalSwitchgear com ...
Page 16: ...Courtesy of NationalSwitchgear com ...
Page 40: ...Courtesy of NationalSwitchgear com ...
Page 74: ...Courtesy of NationalSwitchgear com ...
Page 146: ...Courtesy of NationalSwitchgear com ...
Page 186: ...Courtesy of NationalSwitchgear com ...
Page 220: ...Courtesy of NationalSwitchgear com ...
Page 304: ...Courtesy of NationalSwitchgear com ...
Page 340: ...Courtesy of NationalSwitchgear com ...
Page 380: ...Courtesy of NationalSwitchgear com ...
Page 450: ...Courtesy of NationalSwitchgear com ...
Page 506: ...Courtesy of NationalSwitchgear com ...
Page 528: ...Courtesy of NationalSwitchgear com ...
Page 534: ...Courtesy of NationalSwitchgear com ...
Page 536: ...Courtesy of NationalSwitchgear com ...
Page 550: ...Courtesy of NationalSwitchgear com ...
Page 562: ...Courtesy of NationalSwitchgear com ...
Page 570: ...Courtesy of NationalSwitchgear com ...
Page 584: ...Courtesy of NationalSwitchgear com ...
Page 602: ...Courtesy of NationalSwitchgear com ...