6-16
Close and Reclose Logic
Date Code 20001006
SEL-351 Instruction Manual
Close Logic Can Still Operate When the Reclosing Relay is Defeated
If the reclosing relay is defeated, the close logic (see Figure 6.1) can still operate if SEL
OGIC
Control Equation circuit breaker status setting 52A is set to something other than numeral 0.
Making the setting 52A = 0 defeats the close logic and also defeats the reclosing relay.
For example, if 52A = IN1, a 52a circuit breaker auxiliary contact is connected to input IN1. If
the reclosing relay does not exist, the close logic still operates, allowing closing to take place via
SEL
OGIC
Control Equation setting CL (close conditions, other than automatic reclosing). See
Close Logic
earlier in this section for more discussion on SEL
OGIC
Control Equation settings 52A
and CL. Also see
Optoisolated Inputs
in
Section 7: Inputs, Outputs, Timers, and Other
Control Logic
for more discussion on SEL
OGIC
Control Equation setting 52A.
Reclosing Relay Timer Settings
The open interval and reset timer factory settings are shown in Table 6.2:
Table 6.2: Reclosing Relay Timer Settings and Setting Ranges
Timer
Setting (range)
Factory Setting
(in cycles)
Definition
79OI1 (0.00 - 999999 cyc)
30.00
open interval 1 time
79OI2 (0.00 - 999999 cyc)
600.00
open interval 2 time
79OI3 (0.00 - 999999 cyc)
0.00
open interval 3 time
79OI4 (0.00 - 999999 cyc)
0.00
open interval 4 time
79RSD (0.00 - 999999 cyc)
1800.00
reset time from reclose cycle state
79RSLD (0.00 - 999999 cyc)
300.00
reset time from lockout state
The operation of these timers is affected by SEL
OGIC
Control Equation settings discussed later in
this section. Also see the settings sheets at the end of
Section 9: Setting the Relay
.
Open Interval Timers
The reclose enable setting, E79, determines the number of open interval time settings that can be
set. For example, if setting E79 = 3, the first three open interval time settings in Table 6.2, are
made available for setting.
If an open interval time is set to zero, then that open interval time is not operable, and neither are
the open interval times that follow it.
In the factory settings in Table 6.2, the open interval 3 time setting 79OI3 is the first open interval
time setting set equal to zero:
79OI3
= 0.00 cycles
Summary of Contents for SEL-351
Page 14: ...Courtesy of NationalSwitchgear com ...
Page 16: ...Courtesy of NationalSwitchgear com ...
Page 40: ...Courtesy of NationalSwitchgear com ...
Page 74: ...Courtesy of NationalSwitchgear com ...
Page 146: ...Courtesy of NationalSwitchgear com ...
Page 186: ...Courtesy of NationalSwitchgear com ...
Page 220: ...Courtesy of NationalSwitchgear com ...
Page 304: ...Courtesy of NationalSwitchgear com ...
Page 340: ...Courtesy of NationalSwitchgear com ...
Page 380: ...Courtesy of NationalSwitchgear com ...
Page 450: ...Courtesy of NationalSwitchgear com ...
Page 506: ...Courtesy of NationalSwitchgear com ...
Page 528: ...Courtesy of NationalSwitchgear com ...
Page 534: ...Courtesy of NationalSwitchgear com ...
Page 536: ...Courtesy of NationalSwitchgear com ...
Page 550: ...Courtesy of NationalSwitchgear com ...
Page 562: ...Courtesy of NationalSwitchgear com ...
Page 570: ...Courtesy of NationalSwitchgear com ...
Page 584: ...Courtesy of NationalSwitchgear com ...
Page 602: ...Courtesy of NationalSwitchgear com ...