6-14
Close and Reclose Logic
Date Code 20001006
SEL-351 Instruction Manual
Lockout State
The reclosing relay goes to the Lockout State if any one of the following occurs:
•
The shot counter is equal to or greater than the last shot at time of reclose initiation
(e.g., all automatic reclosing attempts are unsuccessful — see Figure 6.6).
•
Reclose initiation is unsuccessful because of SEL
OGIC
Control Equation setting 79RIS
[see
Reclose Initiate and Reclose Initiate Supervision Settings (79RI and 79RIS,
respectively)
later in this subsection].
•
The circuit breaker opens without reclose initiation (e.g., an external trip).
•
The shot counter is equal to or greater than last shot, and the circuit breaker is open [e.g.,
the shot counter is driven to last shot with SEL
OGIC
Control Equation setting 79DLS
while open interval timing is in progress. See
Drive-to-Lockout and Drive-to-Last Shot
Settings (79DTL and 79DLS, respectively)
later in this subsection].
•
The close failure timer (setting CFD) times out (see Figure 6.1).
•
SEL
OGIC
Control Equation setting 79DTL = logical 1 [see
Drive-to-Lockout and Drive-
to-Last Shot Settings (79DTL and 79DLS, respectively)
later in this subsection].
•
The Reclose Supervision Limit Timer (setting 79CLSD) times out (see Figure 6.2 and top
of Figure 6.3).
Note:
OPEN Command no longer embedded in Drive-to-Lockout Logic
In previous firmware versions of the SEL-351 Relay (except the original release), the
OPEN command was embedded to drive the reclosing relay to lockout (see
Appendix A
).
The OPEN command is no longer directly embedded in the reclosing relay logic. It is also
no longer directly embedded in the trip logic (see the Note following Figure 5.2).
This change was made so that users can supervise the OPEN command if desired (see the
example in the Note following Figure 5.2).
The OPEN command is now included in the reclosing relay logic via the factory SEL
OGIC
Control Equation settings:
79DTL = … + OC
(drive-to-lockout)
Relay Word bit OC asserts for execution of the OPEN Command. See OPE Command
(Open Breaker) in
Section 10: Serial Port Communications and Commands
for more
information on the OPEN Command. Also, see
Drive-to-Lockout and Drive-to-Last Shot
Settings (79DTL and 79DLS, respectively)
later in this subsection.
If the OPEN command is set to trip (TR = … + OC; see Note following Figure 5.2), then
the following reclosing relay SEL
OGIC
Control Equation settings should also be made
(presuming that an OPEN command trip should not initiate reclosing):
79RI = TRIP
(reclose initiate)
79DTL = … + OC
(drive-to-lockout)
This is how the SEL-351 Relay is set at the factory.
Summary of Contents for SEL-351
Page 14: ...Courtesy of NationalSwitchgear com ...
Page 16: ...Courtesy of NationalSwitchgear com ...
Page 40: ...Courtesy of NationalSwitchgear com ...
Page 74: ...Courtesy of NationalSwitchgear com ...
Page 146: ...Courtesy of NationalSwitchgear com ...
Page 186: ...Courtesy of NationalSwitchgear com ...
Page 220: ...Courtesy of NationalSwitchgear com ...
Page 304: ...Courtesy of NationalSwitchgear com ...
Page 340: ...Courtesy of NationalSwitchgear com ...
Page 380: ...Courtesy of NationalSwitchgear com ...
Page 450: ...Courtesy of NationalSwitchgear com ...
Page 506: ...Courtesy of NationalSwitchgear com ...
Page 528: ...Courtesy of NationalSwitchgear com ...
Page 534: ...Courtesy of NationalSwitchgear com ...
Page 536: ...Courtesy of NationalSwitchgear com ...
Page 550: ...Courtesy of NationalSwitchgear com ...
Page 562: ...Courtesy of NationalSwitchgear com ...
Page 570: ...Courtesy of NationalSwitchgear com ...
Page 584: ...Courtesy of NationalSwitchgear com ...
Page 602: ...Courtesy of NationalSwitchgear com ...