2-20
Installation
Date Code 20001006
SEL-351 Instruction Manual
1. Voltage Channel VS does not need to be connected. It is used only in voltage and synchronism check elements
and voltage metering.
2. In this example, current Channel IN provides current polarization for a directional element used to control ground
overcurrent elements. Separate from Channel IN, the residual ground overcurrent elements operate from the
internally derived residual current I
G
(I
G
= 3I
0
= I
A
+ I
B
+ I
C
).
Figure 2.10: SEL-351 Relay Provides Directional Overcurrent Protection and Reclosing for
a Transmission Line (Current
-
Polarization Source Connected to Channel IN)
Summary of Contents for SEL-351
Page 14: ...Courtesy of NationalSwitchgear com ...
Page 16: ...Courtesy of NationalSwitchgear com ...
Page 40: ...Courtesy of NationalSwitchgear com ...
Page 74: ...Courtesy of NationalSwitchgear com ...
Page 146: ...Courtesy of NationalSwitchgear com ...
Page 186: ...Courtesy of NationalSwitchgear com ...
Page 220: ...Courtesy of NationalSwitchgear com ...
Page 304: ...Courtesy of NationalSwitchgear com ...
Page 340: ...Courtesy of NationalSwitchgear com ...
Page 380: ...Courtesy of NationalSwitchgear com ...
Page 450: ...Courtesy of NationalSwitchgear com ...
Page 506: ...Courtesy of NationalSwitchgear com ...
Page 528: ...Courtesy of NationalSwitchgear com ...
Page 534: ...Courtesy of NationalSwitchgear com ...
Page 536: ...Courtesy of NationalSwitchgear com ...
Page 550: ...Courtesy of NationalSwitchgear com ...
Page 562: ...Courtesy of NationalSwitchgear com ...
Page 570: ...Courtesy of NationalSwitchgear com ...
Page 584: ...Courtesy of NationalSwitchgear com ...
Page 602: ...Courtesy of NationalSwitchgear com ...