22 of 44
496339 Issue 4
Note: An IDIS LIM contains the equivalent of five IDIS devices, numbered consecu-
tively. When programming a LIM the system automatically assigns a block of
five consecutive zone numbers. Therefore, program the first IDIS device in the
LIM to the lowest zone number.
Do not try to program the other four de-
vices
, the system will do it for you.
11. Disconnect programmed IDIS module/sensor.
12. Write the zone number on the device, so that it will be installed in the
correct position.
13. Repeat steps 4 to 12 for the other modules to be programmed.
14. Press Menu when IDIS programming is complete.
The display shows Menu 22.
IDIS Programming Errors
You may see one of the following messages on the second line of the display
while programming IDIS modules/sensors. If so follow the procedure indi-
cated.
OUT OF RANGE
The module is blank or incorrectly programmed.
Carry on and try to program the module. If you do
not succeed then use a new device and return the
original to the manufacturer.
NOT IDIS ZONE
You have tried to program a zone number less than
9. Zones 1 to 8 are FSL zones.
NO DEVICE FOUND
There is nothing connected to the programming
pins on the IDIS Expander card.
DEVICE FAULTY
The system failed to program the device. Try again
to program the module. If you do not succeed then
use a new device and return the original to the
manufacturer.
FREQUENCY ERROR
The device or module is not programmed correctly.
Try again to program the module. If you do not
succeed then use a new device and return the
original to the manufacturer.
NON SCANTRONIC
The module is not a Scantronic IDIS device. The
module cannot be used.
IDIS Programming Errors
8136
Summary of Contents for 8136UK-50
Page 44: ...44 of 44 496339 Issue 4 ...