General Faults
No response from the keypad keys.
•
Check the keypad wiring.
•
Check the keypad address programming. See "Keypads".
•
Enter and leave programming mode.
•
Power up while shorting RST pins. (See "Resetting User and Installer
Codes".)
No exit/entry tones from remote keypad
•
Check keypad is addressed correctly. See "Keypads".
•
Check that Keypad Sounder is ‘Enabled’. See "Keypads".
•
Check keypad is assigned to the Level being set (Menu 47).
•
Check if keypad faulty.
Manual Connect from the remote PC fails to operate.
•
Check Secure Call Back is ‘Disabled’ (menu 73).
Cannot remotely Set/Unset system
•
Check Remote Set/Unset ‘Enabled’. Refer to user Menu 3 - ‘System
Options’. (Note that the Installer Code does not allow you access to
User Menu 3.)
Error Messages
At various points in programming you may see error messages on the
display. The majority are self explanatory. The following list shows those that
are more obscure.
Configuration Checking Error Messages
The end station checks the configuration when you exit programming mode
or when you apply power. If the end station finds a configuration error during
power up it displays the message "CONFIGURATION ERROR CALL ENGI-
NEER" at the keypad. The panel is unusable until you cure the problem.
(Note that this will only occur if you have removed power from the end station
while in programming mode with a configuration error.)
The end station will not let you leave programming mode until you have cured
a configuration error.
The first line of the configuration checking error message always shows the
words "CHECK CONFIG". The second line of the display may show one of
the following:
Error Messages
8136