32 of 44
496339 Issue 4
NON KEY Z IN LA
Meaning: No Keyswitch Zone In Level. In the example shown Level A has
been assigned a keyswitch zone which is not a keyswitch zone
type.
Action:
Check Menu 41 or 32.
KEYSWITCH ZONES
Meaning: Keyswitch Zone Assigned to Different Levels. In the example
shown a keyswitch zone has been assigned to the same option for
two Levels within the same Partition.
Action:
Check Menu 41.
SIA DUAL REPORT
Meaning: Dual Reporting and SIA Format have both been selected at the
same time. The system does not allow this.
Action:
Check Menu 71
TR ZONE 18
Meaning: Two sequentially numbered zones have been programmed as
Trouble. In the example shown zone 18 is one of the zones.
Action:
Check Menu 32.
FSL Zone Status Error Messages
Z01:FSL STATUS
1K9 (TROUBLE)
Meaning: FSL Loop Resistance Wrong. The loop resistance on one of the
FSL loops is above or below the normal threshold Level. Zones in
trouble will not prevent a user from setting the system, however, the
system displays the 'call engineer' message when the user tries to
set the system.
Action:
•
Test FSL Zone status. Possible causes are loose or corroded
connections and high resistance.
•
Check all wiring and connections associated with the zone(s) in
trouble.
IDIS Error Messages
ZONE 09 MISSING
Meaning: Menu 33 IDIS zones ‘MISSING’. The end station has tried to
initialise all valid IDIS modules/sensors and has failed.
Action:
See "IDIS Fault Finding".
FSL Zone Status Error Messages
8136
Summary of Contents for 8136UK-50
Page 44: ...44 of 44 496339 Issue 4 ...