The low and high values of these set points may be assigned either to (regardless of the operating mode):
gross measurement
net measurement
Sensor input control result
Batch
10.2.3
Motion:
The outputs can be assigned to copying measurements stability.
10.2.4
Defective measurement:
The output level is set when the internal alarm flag described in “Weighing diagnosis” § in the MEASUREMENT AND STATUS §
is activated. This allows to warn about defection of the measurement chain. Flowrate alarms are not considered as defective
measurements.
10.2.5
Input image:
Outputs can be assigned to copying inputs state, either using the same logic or inverting the input state (negative logic).
Outputs 1 and 3 are assigned to input 1&3 and outputs 2 and 4 are assigned to input 2&4.
10.2.6
Level on request:
The input level is driven by master requests.
10.3
Functions attached to an operating mode:
See corresponding sections for a complete description.
10.4
Optional analog output (IO+ version)
An optional analog board in
current
and
voltage
might be used with
eNod4
to provide IO+ version. This must be asked when
ordering
eNod4
product.
Voltage output might be set either 0-5V or 0-10V, and the current output to 4-20mA, 0-24mA, 0-20mA or 4-20mA with alarm
at 3.6mA. Both output (current and voltage) might separately be enable. Settings are effective after
eNod4
reset.
Analog output affectation function is common to both
current
and
voltage
output and might be assigned to followings: