INSTALLING THE AT10.1
23
Note the following:
•
You should set the Float and Equalize voltages to the values
recommended by your battery manufacturer for 77 °F / 25 °C.
•
When you enter the
Edit Mode
to adjust the Float or Equalize voltage
(see Section 2.3.2), the front panel meter displays the 77 °F / 25 °C value
for the Float or Equalize voltage, even if the battery is warmer or cooler
than 77 °F / 25 °C.
•
The actual output voltage of the AT10.1 may be different from the value
displayed on the front panel meter, if the battery is warmer or cooler than
77 °F / 25 °C.
•
Use a digital meter to measure the actual output voltage of the AT10.1.
If you know the temperature at the temperature compensation probe, you
can use the graph below to determine that the output voltage is correct.
•
If the battery temperature goes below 32 °F / 0 °C, there will be no
further increase in AT10.1 output voltage. Likewise, if the battery
temperature goes above 122 °F / 50 °C, there is no further decrease in
output voltage.
O U T P U T V O L T A G E VS B A T TE R Y T E M P E R A T U R E
9 4
9 6
9 8
1 0 0
1 0 2
1 0 4
1 0 6
1 0 8
20
4 0
6 0
80
1 0 0
12 0
T e m p e r a tur e , D e g r e e s F a h r e n h e it
P
e
rcen
t O
u
tp
u
t V
o
lt
ag
e
L e a d -Aci d
N icke l-C a d m iu m
E xa m p l e :
1 0 0 D e g . F
9 7 % O u tp u t
V o lta g e
EXAMPLE: Suppose you have a lead-acid battery whose temperature is
100 °F / 37.8 °C. As shown on the graph, the output voltage should be
approximately 97% of the 77 °F voltage. If the float voltage is set on the
front panel to 132 Vdc, the actual output voltage will be:
132 x 0.97 =
128 Vdc
1.12. INSTALLING FOR REMOTE COMMUNICATION
(OPTIONAL)
Refer to separate
Operating Instructions
(
JA0102-04
).
1.13. INSTALLING FOR FORCED LOAD SHARING
(OPTIONAL)
Refer to Appendix F on page 92 or
Operating Instructions
(
JA5054-00
).
Summary of Contents for AT10.1 SERIES
Page 78: ...APPENDIX C 72 Outline AT10 1 Group II Battery Charger NEMA 1 Style 5017 Enclosure JE5025 00...
Page 79: ...APPENDIX C 73 http www ATSeries net PDFs JE5025 00 pdf...
Page 80: ...APPENDIX C 74 Outline AT10 1 Group II Battery Charger NEMA 1 Style 5018 Enclosure JE5026 00...
Page 81: ...APPENDIX C 75 http www ATSeries net PDFs JE5026 00 pdf...
Page 83: ...APPENDIX C 77 http www ATSeries net PDFs JE5028 99 pdf...
Page 85: ...APPENDIX C 79 http www ATSeries net PDFs JE5029 99 pdf...
Page 87: ...APPENDIX C 81 http www ATSeries net PDFs JE5030 29 pdf...
Page 88: ...APPENDIX C 82 Schematic AT10 1 Group II Battery Charger Standard w o Options JE5032 00...
Page 89: ...APPENDIX C 83 http www ATSeries net PDFs JE5032 00 pdf...
Page 90: ...APPENDIX C 84 Schematic AT10 1 Group II Battery Charger w Common Options JE5032 99...
Page 91: ...APPENDIX C 85 http www ATSeries net PDFs JE5032 99 pdf...
Page 93: ...APPENDIX C 87 http www ATSeries net PDFs JE5034 00 pdf...
Page 94: ...APPENDIX C 88 Connection Diagram AT10 1 Group II Battery Charger w Common Options JE5034 99...
Page 95: ...APPENDIX C 89 http www ATSeries net PDFs JE5034 99 pdf...
Page 101: ...USER NOTES 95...