APPENDIX F
92
FORCED LOAD SHARING
ONLINE SUPPLEMENT
http://www.ATSeries.net/PDFs/JA5054-00.pdf
INTRODUCTION
Multiple battery chargers are sometimes employed in dc power systems to provide
redundancy. Two (2) or more chargers of the same voltage rating can be connected in parallel, each
of them capable of powering the connected dc load and charging the battery. If a battery charger
should fail during normal operation, the parallel charger can continue to supply the entire required
dc load current, and maintain charge on the battery.
When two (2) AT10.1s operate in parallel, they normally will not share the load current
equally. Since any two chargers will have slightly different characteristics, one of the two chargers
in a system will have a slightly higher dc output voltage, and will therefore assume more of the
burden of providing necessary load current. This section describes an optional accessory for the
AT10.1, which
forces
units to share dc load equally. The accessory (ordering p/n EJ5126-##)
consists of an interconnecting cable to provide such communication, and operating instructions.
SYSTEM REQUIREMENTS
•
The forced load sharing feature is designed only to work with two (2) AT10.1 Series battery
chargers. You cannot force load sharing with three (3) or more AT10.1s.
•
Both AT10.1s must have the same dc voltage & current rating, and have the same dc filtering.
•
Both AT10.1s must have the same ac input source and the same phase rotation.
•
Both AT10.1s must feature
Rev. 6
(or higher) builds of the Main Control PC Boards (A1), and
corresponding (Rev. 6 or higher) software programs.
•
Both AT10.1s must use the same the same program version, since the forced load sharing option
has not been tested using different program versions in each unit. To view the program version,
press the
LAMP TEST
button on the front instrument panel of the AT10.1. When you release
the button, the front panel meter displays the version number for 2 seconds.
•
The interconnecting signal cable length should be no more than 50ft (15m).
INSTALLING THE INTERCONNECTION CABLE
The AT Series forced load sharing accessory is normally supplied by the factory with a
standard 15ft (4.6m) interconnection cable. A 25ft (7.6m) long cable and a 50ft (15.2m) long cable
are also available. The interconnection cable is terminated at each end with a 6-pin connector that
mates with the plastic connector (J4) on lower-right corner of the Main Control PC Board (A1). One
end of the cable features an extra jumper in the connector, and should be identified for use with the
Secondary
charger. The other end of the cable connects to the
Primary
charger. Either AT10.1 may
be selected as Primary or Secondary, but you may wish to choose the unit that is more accessible to
be the Primary. The Primary charger controls the dc output voltage of both AT10.1s.
You may run the interconnection cable through conduit if necessary. However, do not run
the cable through the same conduit with power wiring. Do not remove the connectors in order to
"fish" the cable through the conduit. Maximum pulling tension is 46 lb. (20.9kg). The cable has a
plenum-rated outer jacket, and passes the NFPA 262 flame propagation test. Install the cable
between the AT10.1s, and anchor it in place at both ends before connecting. Connect each end to
the Main Control PC Boards (A1), inserting the connector into J4 until it is completely seated.
NOTICE
Power cabling for the battery charger, battery, and dc load interconnection is
not
supplied
with the AT10.1 or the AT Series Forced Load sharing option. All user-supplied system wiring
should meet National Electric Code (NEC) standards, as well as local/site codes. Confirm polarity
of all dc cabling before making connections.
Summary of Contents for AT10.1 SERIES
Page 78: ...APPENDIX C 72 Outline AT10 1 Group II Battery Charger NEMA 1 Style 5017 Enclosure JE5025 00...
Page 79: ...APPENDIX C 73 http www ATSeries net PDFs JE5025 00 pdf...
Page 80: ...APPENDIX C 74 Outline AT10 1 Group II Battery Charger NEMA 1 Style 5018 Enclosure JE5026 00...
Page 81: ...APPENDIX C 75 http www ATSeries net PDFs JE5026 00 pdf...
Page 83: ...APPENDIX C 77 http www ATSeries net PDFs JE5028 99 pdf...
Page 85: ...APPENDIX C 79 http www ATSeries net PDFs JE5029 99 pdf...
Page 87: ...APPENDIX C 81 http www ATSeries net PDFs JE5030 29 pdf...
Page 88: ...APPENDIX C 82 Schematic AT10 1 Group II Battery Charger Standard w o Options JE5032 00...
Page 89: ...APPENDIX C 83 http www ATSeries net PDFs JE5032 00 pdf...
Page 90: ...APPENDIX C 84 Schematic AT10 1 Group II Battery Charger w Common Options JE5032 99...
Page 91: ...APPENDIX C 85 http www ATSeries net PDFs JE5032 99 pdf...
Page 93: ...APPENDIX C 87 http www ATSeries net PDFs JE5034 00 pdf...
Page 94: ...APPENDIX C 88 Connection Diagram AT10 1 Group II Battery Charger w Common Options JE5034 99...
Page 95: ...APPENDIX C 89 http www ATSeries net PDFs JE5034 99 pdf...
Page 101: ...USER NOTES 95...