OPERATING THE AT10.1
35
Using Ground Detection in Charger Standby Mode
If you put the AT10.1 into standby mode by opening the dc circuit breaker
(CB2), the ground detection circuit will send an erroneous
positive (+)
ground fault alarm. There are two (2) ways to work around this:
•
Disable the ground detection circuit while the AT10.1 is in standby, as
described below.
•
Put the AT10.1 into standby by opening the ac input circuit breaker
(CB1), and leaving the dc circuit breaker (CB2) closed.
Operating the AT10.1 with the ac breaker (CB1) closed, but the dc
breaker (CB2) open, is an
abnormal
condition. It is not recommended.
Disabling the Ground Detection Alarm
You can disable the ground detection alarm circuit, and isolate the circuit
from chassis ground. If your battery is normally grounded, or you want to
defeat the alarm for any other reason, follow these steps:
•
Shut down the AT10.1 and lock out all ac and dc voltage sources. This
includes alarm and remote sense wires if they were installed. Open the
front panel door and check with a voltmeter before proceeding.
•
Locate jumper
J5
at the top left of the Main Control PC Board (A1) as
shown on the previous page. Move the jumper to the
DISABLE
position. The
POS GND
and
NEG GND
indicators and the summary
alarm relay (TB3) will not respond to a ground fault.
Restart the AT10.1, following the instructions in Section 2.1.
2.3.5. Setting the Current Limit value
The AT10.1 automatically limits its dc output current in case of overload
or battery discharge. You can adjust the value of the Current Limit from
50% to 110% of rated current. The factory setting is 110%.
The Current Limit adjustment is the last step in the normal
Edit Mode
sequence. If the AT10.1 is not in the
Edit Mode
, press the
EDIT/ENTER
key
six (6) times, until the meter display flashes the value of the Current Limit
setting (in Amperes). Press and release the
UP
or
DOWN
key to increase or
decrease the value in the display by one count, or press and hold the
UP
or
DOWN
key to scroll the value in the display upward or downward. When
the meters display the desired Current Limit value, release the
UP
or
DOWN
key. If you go past the number you want, press the
UP
or
DOWN
key again
to reach the number you want to set.
•
Press the
EDIT/ENTER
key.
•
The new Current Limit setting is saved internally.
•
The front panel display will flash
End
to confirm.
If you do not press any front panel key for 25 seconds,
Edit Mode
ends
automatically, and any change you made to the last setting is not saved.
Summary of Contents for AT10.1 SERIES
Page 78: ...APPENDIX C 72 Outline AT10 1 Group II Battery Charger NEMA 1 Style 5017 Enclosure JE5025 00...
Page 79: ...APPENDIX C 73 http www ATSeries net PDFs JE5025 00 pdf...
Page 80: ...APPENDIX C 74 Outline AT10 1 Group II Battery Charger NEMA 1 Style 5018 Enclosure JE5026 00...
Page 81: ...APPENDIX C 75 http www ATSeries net PDFs JE5026 00 pdf...
Page 83: ...APPENDIX C 77 http www ATSeries net PDFs JE5028 99 pdf...
Page 85: ...APPENDIX C 79 http www ATSeries net PDFs JE5029 99 pdf...
Page 87: ...APPENDIX C 81 http www ATSeries net PDFs JE5030 29 pdf...
Page 88: ...APPENDIX C 82 Schematic AT10 1 Group II Battery Charger Standard w o Options JE5032 00...
Page 89: ...APPENDIX C 83 http www ATSeries net PDFs JE5032 00 pdf...
Page 90: ...APPENDIX C 84 Schematic AT10 1 Group II Battery Charger w Common Options JE5032 99...
Page 91: ...APPENDIX C 85 http www ATSeries net PDFs JE5032 99 pdf...
Page 93: ...APPENDIX C 87 http www ATSeries net PDFs JE5034 00 pdf...
Page 94: ...APPENDIX C 88 Connection Diagram AT10 1 Group II Battery Charger w Common Options JE5034 99...
Page 95: ...APPENDIX C 89 http www ATSeries net PDFs JE5034 99 pdf...
Page 101: ...USER NOTES 95...