INSTALLING THE AT10.1
8
1.5.3. Rack-Mounting the AT10.1
The AT10.1 can be installed in most relay racks with standard EIA hole
spacing. The Style-5017 and Style-5018 enclosures do not need to be
modified for rack mounting, but a special kit (
EI0193-0#
) is required.
For kit availability see the ordering information in Appendix B on page
71. The kit includes two (2) mounting brackets, necessary hardware, and
Installation Instructions
(
JA0091-02
/
JA0091-03
) for the rack-
mounting procedure. Refer to the table below for allowable combinations.
RACK WIDTH
CHARGER RATING
Voltage Current
19in / 483mm
23-24in /
584-610mm
12 Vdc
30-50 Adc
EI0193-01
EI0193-02
12 Vdc
75-100 Adc
n/a
EI0193-03
24 Vdc
30-50 Adc
EI0193-01
EI0193-02
24 Vdc
75-100 Adc
n/a
EI0193-03
48 Vdc
30-40 Adc
EI0193-01
EI0193-02
48 Vdc
50-100 Adc
n/a
EI0193-03
130 Vdc
30 Adc
EI0193-01
EI0193-02
130 Vdc
40-75 Adc
n/a
EI0193-03
MOUNTING KIT
When rack-mounting the AT10.1, consider the following:
1. The rack must be strong enough to properly support the weight of the
AT10.1. See the Weight Table located in Section 1.4 on page 3.
2. Be conscious of planned ac input and dc output wiring to the AT10.1,
selecting conduit entrances carefully. Note the standard pre-fab conduit
knockouts located on the sides of the enclosures. Ensure that planned
conduit is accessible after the AT10.1 is rack-mounted.
3. The
location:
•
Should be free of drips and splatter. If falling particles and liquids are a
problem, install a NEMA-2 type drip shield accessory (
EI0191-0#
). For
kit availability, see ordering information in Appendix B on page 71.
•
Should be between 0 and 122 °F / -18 and 50 °C, with relative humidity
between 5% and 95% non-condensing.
•
Must be free of flammable or explosive materials.
4. Maintain at least 6in / 152mm of free air on all vented surfaces for cooling.
5. Allow at least 36in / 914mm front clearance for access to the AT10.1 for
operation and maintenance.
Summary of Contents for AT10.1 SERIES
Page 78: ...APPENDIX C 72 Outline AT10 1 Group II Battery Charger NEMA 1 Style 5017 Enclosure JE5025 00...
Page 79: ...APPENDIX C 73 http www ATSeries net PDFs JE5025 00 pdf...
Page 80: ...APPENDIX C 74 Outline AT10 1 Group II Battery Charger NEMA 1 Style 5018 Enclosure JE5026 00...
Page 81: ...APPENDIX C 75 http www ATSeries net PDFs JE5026 00 pdf...
Page 83: ...APPENDIX C 77 http www ATSeries net PDFs JE5028 99 pdf...
Page 85: ...APPENDIX C 79 http www ATSeries net PDFs JE5029 99 pdf...
Page 87: ...APPENDIX C 81 http www ATSeries net PDFs JE5030 29 pdf...
Page 88: ...APPENDIX C 82 Schematic AT10 1 Group II Battery Charger Standard w o Options JE5032 00...
Page 89: ...APPENDIX C 83 http www ATSeries net PDFs JE5032 00 pdf...
Page 90: ...APPENDIX C 84 Schematic AT10 1 Group II Battery Charger w Common Options JE5032 99...
Page 91: ...APPENDIX C 85 http www ATSeries net PDFs JE5032 99 pdf...
Page 93: ...APPENDIX C 87 http www ATSeries net PDFs JE5034 00 pdf...
Page 94: ...APPENDIX C 88 Connection Diagram AT10 1 Group II Battery Charger w Common Options JE5034 99...
Page 95: ...APPENDIX C 89 http www ATSeries net PDFs JE5034 99 pdf...
Page 101: ...USER NOTES 95...