Appendix: Technical Specifications
45
Measurement Specifications
Accuracy, %
Range
Display resolution (%Rdg)
Parameter
Full scale
Rdg FS Conditions
@
range
Voltage
120V
×
PT
@ 120V
400V
×
PT
@ 690V
208V
×
PT
@ 120V
690V
×
PT
@ 690V
0.3 10% to 120% FS 0 to 999,000 V
1 V @ 1V to 9,999 V
≤
0.1% @ 10,000 V to 999,000 V
Starting voltage 1.5% FS
Line current
CT PRIMARY CURRENT
0.3 2% to 150% FS
0 to 60,000 A
1 A @ 1A to 9,999 A
≤
0.1% @ 10,000 A to 60,000 A
Starting current 0.75% FS
Active power
0.36
×
PT
×
CT @ 120V input
1.2
×
PT
×
CT @ 690V input
0.5
|PF|
≥
0.5
-2,000,000 to
+2,000,000 kW
1 kW @ 1kW to 9,999 kW
≤
0.1% @ 10 MW to 2,000 MW
Reactive power
0. 36
×
PT
×
CT @ 120V input
1.2
×
PT
×
CT @ 690V input
0.5
|PF|
≤
0.9
-2,000,000 to
+2,000,000 kvar
1 kvar @ 1kvar to 9,999 kvar
≤
0.1% @ 10 Mvar to 2,000 Mvar
Apparent power
0. 36
×
PT
×
CT @ 120V input
1.2
×
PT
×
CT @ 690V input
0.5
|PF|
≥
0.5
0 to
2,000,000 kVA
1 kVA @ 1kVA to 9,999 kVA
≤
0.1% @ 10 MVA to 2,000 MVA
Power factor
1
1
|PF|
≥
0.5,
U
≥
10% FSU
I
≥
10% FS
I
-0.999 to +1.000
0.001
Frequency
0.1
45.00 to 65.00 Hz
0.01 Hz
or
or
For
Ln
reading
and for
3OP2/3OP3
wiring
modes
For
LL
reading except
3OP2/3OP3
wiring modes
Summary of Contents for PM130E
Page 1: ...Se Series PM130 Powermeters Installation and Operation Manual BG0306 Rev A1 ...
Page 2: ...Series PM130 Powermeters Installation and Operation Manual ...
Page 6: ...iv Quick Start TYPICAL INSTALLATION see Section 2 2 4 for full instructions Wiring Mode 4LL3 ...
Page 12: ...Chapter 1 Introduction 5 Instrument Dimensions Figure 1 1 PM130 Dimensions ...
Page 14: ...Chapter 2 Installation 7 Figure 2 2 The PM130 Terminations ...
Page 17: ...Chapter 2 Installation 10 Figure 2 4 Current Input Connection ...