4.5 Relay Operation Control Menu
This menu allows you to set the relay operation mode: non-failsafe
or failsafe. Failsafe relay operation is the opposite of normal
operation where relay contacts are closed when a relay is
operated (activated), and are open when a relay is released (de-
activated). In failsafe mode, an alarm is activated by a non-
energized relay which will open in all cases when an alarm
condition is present or an alarm setpoint is not operational either
due to a loss of control power or due to corruption of the setpoint
setup configuration. A failsafe relay is closed only if it is under
setpoint control and no alarm conditions exist, or if it is manually
operated via communications.
To change the relay operation mode:
Press to activate the lower window.
Use the up/down arrow keys to set the desired
option. Select
nor
for normal (non-failsafe) relay
operation, or select
FSAFE
for failsafe relay
operation.
Press to store your new setting or press to
leave your previous setting unchanged.
To quit the setup menu:
From the middle window, press or .
NOTES
1. You will not be able to change the relay operation mode if a relay has
been allocated for pulsing.
2. When a failsafe relay is allocated for pulsing, it automatically reverts
to normal operation.
SELECT
CHG
rELo
ENTER
ENTER
rELo
nor
rEL
ESC
ESC
SELECT
ENTER
ENTER
Summary of Contents for PM130E
Page 1: ...Se Series PM130 Powermeters Installation and Operation Manual BG0306 Rev A1 ...
Page 2: ...Series PM130 Powermeters Installation and Operation Manual ...
Page 6: ...iv Quick Start TYPICAL INSTALLATION see Section 2 2 4 for full instructions Wiring Mode 4LL3 ...
Page 12: ...Chapter 1 Introduction 5 Instrument Dimensions Figure 1 1 PM130 Dimensions ...
Page 14: ...Chapter 2 Installation 7 Figure 2 2 The PM130 Terminations ...
Page 17: ...Chapter 2 Installation 10 Figure 2 4 Current Input Connection ...