Chapter 4 Setup Menus
25
Table 4-5 Setpoint Triggers
(lower window, when middle window is
triG
)
Code
Parameter
Unit Range
nonE Setpoint
disabled
Phase Reversal
POS.ro.
Positive phase rotation reversal
NEG.ro.
Negative phase rotation reversal
Real-time Values on any Phase
r. Hi. U
High voltage
V
0 to Vmax
r. Lo. U
Low voltage
V
0 to Vmax
r. Hi. C
High current
A
0 to Imax
r. Lo. C
Low current
A
0 to Imax
Real-time Auxiliary Measurements
r. Hi.Fr
High frequency
Hz
0 to 100.00
r. Lo.Fr
Low frequency
Hz
0 to 100.00
r. U.Unb
Voltage unbalance
%
0 to 300
r. C.Unb
Current unbalance
%
0 to 300
Average Values per Phase
A. Hi.C1
High current L1
A
0 to Imax
A. Hi.C2
High current L2
A
0 to Imax
A. Hi.C3
High current L3
A
0 to Imax
A. Lo.C1
Low current L1
A
0 to Imax
A. Lo.C2
Low current L2
A
0 to Imax
A. Lo.C3
Low current L3
A
0 to Imax
Average Values on any Phase
A. Hi. U
High voltage
V
0 to Vmax
A. Lo. U
Low voltage
V
0 to Vmax
A. Hi. C
High current
A
0 to Imax
A. Lo. C
Low current
A
0 to Imax
Average Total Values
A. Hi.P.i
High total kW import (positive)
kW 0 to Pmax
A. Hi.P.E
High total kW export (negative)
kW 0 to Pmax
A. Hi.q.i
High total kvar import (positive)
kvar 0 to Pmax
A. Hi.q.E
High total kvar export (negative)
kvar 0 to Pmax
A. Hi. S
High total kVA
kVA 0 to Pmax
A. PF.LG
Low total PF Lag
0 to 1.000
A. PF.Ld
Low total PF Lead
0 to 1.000
Average Auxiliary Measurements
Ar neU.C
High neutral current
A
0 to Imax
Ar Hi.Fr
High frequency
Hz
0 to 100.00
Ar Lo.Fr
Low frequency
Hz
0 to 100.00
Present Demands
Hi d.U1
High volt demand L1
V
0 to Vmax
Hi d.U2
High volt demand L2
V
0 to Vmax
Hi d.U3
High volt demand L3
V
0 to Vmax
Hi d.C1
High ampere demand L1
A
0 to Imax
Hi d.C2
High ampere demand L2
A
0 to Imax
Hi d.C3
High ampere demand L3
A
0 to Imax
P E
P E
P E
P E
P E
P E
Summary of Contents for PM130E
Page 1: ...Se Series PM130 Powermeters Installation and Operation Manual BG0306 Rev A1 ...
Page 2: ...Series PM130 Powermeters Installation and Operation Manual ...
Page 6: ...iv Quick Start TYPICAL INSTALLATION see Section 2 2 4 for full instructions Wiring Mode 4LL3 ...
Page 12: ...Chapter 1 Introduction 5 Instrument Dimensions Figure 1 1 PM130 Dimensions ...
Page 14: ...Chapter 2 Installation 7 Figure 2 2 The PM130 Terminations ...
Page 17: ...Chapter 2 Installation 10 Figure 2 4 Current Input Connection ...