Chapter 5 Data Display
39
Page Window Indicator
LED
Parameter Digits
Unit
11 1
MVAh
AP.En.
Label
11 2
L2
Label
11 3
MVAh
L2
5
MVAh
12 1
MWh
Ac.En.
Label
12 2
IP.L3
Label
12
3
MWh import L3
5
MWh
13 1
Mvarh
rE.En.
Label
13 2
IP.L3
Label
13
3
Mvarh import L3
5
Mvarh
14 1
MVAh
AP.En.
Label
14 2
L3
Label
14 3
MVAh
L3
5
MVAh
Display readings for all electrical quantities except Min/Max log and
energies are sliding average values.
Voltage and current readings with a decimal point are displayed in kV and
kA. Power readings with a decimal point are displayed in MW, Mvar, and
MVA. When the value width is over the window resolution, the right most
digits are truncated.
By default, the maximum range for energy readings is 99,999,999
MWh/Mvarh/MVAh. Beyond this value, the reading will roll over to zero.
When the energy reading exceeds the window resolution, the right-most
digits are truncated. To avoid truncation, you can change the energy roll
value to lower limit via the
User Selectable Options
menu (see Section
4.7). Negative (exported) energy readings are displayed without a sign.
Per phase power and power factor readings are displayed only in
4LN3/4LL3 and 3LN3/3LL3 wiring modes (see Section 4.1) if the phase
powers display is enabled in the
Display Setup
menu (see Section 4.6).
Phase energy readings are displayed only in 4LN3/4LL3 and 3LN3/3LL3
wiring modes if they are enabled in the
User Selectable Options
menu (see
Section 4.7).
When the 4LN3 or 3LN3 wiring mode is selected, the voltages will be line-
to-neutral; for any other wiring mode, they will be line-to-line voltages.
Displayed only in the 4LN3 or 3LN3 wiring mode.
5.3 Self-Test Diagnostics Display
The
PM130
periodically performs self-test diagnostics during
operation. If the instrument fails the test, it discards the last
measurement results, and an error code is displayed for one
second on all LEDs. Error codes are listed in Table 5-3. Code ‘8’
indicates normal operation.
available in the
PM130E
E
Summary of Contents for PM130E
Page 1: ...Se Series PM130 Powermeters Installation and Operation Manual BG0306 Rev A1 ...
Page 2: ...Series PM130 Powermeters Installation and Operation Manual ...
Page 6: ...iv Quick Start TYPICAL INSTALLATION see Section 2 2 4 for full instructions Wiring Mode 4LL3 ...
Page 12: ...Chapter 1 Introduction 5 Instrument Dimensions Figure 1 1 PM130 Dimensions ...
Page 14: ...Chapter 2 Installation 7 Figure 2 2 The PM130 Terminations ...
Page 17: ...Chapter 2 Installation 10 Figure 2 4 Current Input Connection ...