![Satec PM130E Installation And Operation Manual Download Page 47](http://html.mh-extra.com/html/satec/pm130e/pm130e_installation-and-operation-manual_1200370047.webp)
Chapter 5 Data Display
40
Frequent failures may be the result of excessive electrical noise in
the region of the instrument. If the instrument continuously resets
itself, contact your local distributor.
Table 5-3 Self-Test Diagnostic Codes
Code Meaning
1 ROM
error
2 RAM
error
3
Watch dog timer reset
4 Sampling
failure
5
Out of control trap
7 Timing
failure
8
Normal power up
9
External reset (warm restart)
NOTE
The
PM130
provides a self-check alarm register accessible through
communications that indicates possible problems with instrument
hardware or setup configuration. The hardware problems are indicated
by the appropriate bits which are set whenever the instrument fails self-
test diagnostics or in the event of loss of power. The setup
problems are
indicated by the dedicated bit which is set when either configuration
register is corrupted. In this event, your instrument will use the default
configuration. For more information on the self-check alarm register, refer
to the communications reference guides provided with your instrument.
Summary of Contents for PM130E
Page 1: ...Se Series PM130 Powermeters Installation and Operation Manual BG0306 Rev A1 ...
Page 2: ...Series PM130 Powermeters Installation and Operation Manual ...
Page 6: ...iv Quick Start TYPICAL INSTALLATION see Section 2 2 4 for full instructions Wiring Mode 4LL3 ...
Page 12: ...Chapter 1 Introduction 5 Instrument Dimensions Figure 1 1 PM130 Dimensions ...
Page 14: ...Chapter 2 Installation 7 Figure 2 2 The PM130 Terminations ...
Page 17: ...Chapter 2 Installation 10 Figure 2 4 Current Input Connection ...