STEP 8:
WIRING CONNECTIONS
(See Appendix for sample wiring diagrams)
I/O BOARD CONNECTIONS
Position Function
Description
TER
M
IN
AL
STR
IP
J5
1
Electric Lock
Relay
Common
2
Electric Lock
Relay
N.O. Dry contact – Contact closes upon activation. May be used for fail-secure locks
by routing 1 leg of power though the relay. Relay is triggered by activation inputs
10, 11, or 16. Relay remains energized until door is fully closed again.
3
Electric Lock
Relay
N.C. Dry Contact - Contact opens upon activation. May be used for fail-safe locks by
routing 1 leg of power though the relay. Relay is triggered by activation inputs 10,
11, or 16. Relay remains energized until door is fully closed again.
4
Door Status -
Closed
N.O. Contact is closed when door is closed. The contact opens as soon as the door
opens.
5
Door Status –
Common
Common contact for door status
6
Door Status -
Open
N.C. – Contact is closed when door is open. The contact opens as soon as the door
starts to close. This input can be used for motor connection at lockout relay when
power is looped through, thus switching power on when door is open.
TER
M
IN
AL
STR
IP
J4
7
GND
Common GND
8
GND
Common GND
9
+ 24 VDC
1A Max. Current
10
Internal
Activation
Requires N.O. Contact between input 10 & COM. Remains capable to activate when
dip switch 3 is ON AND On-Off switch is OFF.
11
External
Activation
Requires N.O. Contact between input 11 & COM.
12
Emergency
Closing
Requires N.C. contact between 12 & COM. Upon open contact, door closes and
overrides all other inputs. Remains jumpered if input is not used.
13
Secondary
Activation
Requires N.C. contact between 13 & COM. Disabled in full closed position. Used for
AUTO-IR door-mounted presence sensor.
14
Stall Safety
Requires N.C. contact between 14 & COM. Upon open contact, during opening,
door stops, then resumes at reduced speed when input is released.
15
Key Input
N.O. connection
16
Alarm Input
N.O. contact, when closed causes door closing. All inputs inhibited during closed
contact (not available on all software versions)
17
Not Used
Requires N.O. contact
18
GND
Common GND
19
GND
Common GND
20
Aux Relay
Auxiliary Relay COM. NOTE: Relay is triggered by input 16
21
Aux Relay
Auxiliary Relay N.O.
22
Aux Relay
Auxiliary Relay N.C.
23
Alarm Output
- Common
Common
24
Alarm Output N.O. output is closed upon closed contact from fire alarm. LED 2 also illuminates.
25
+ 24 VDC
1A max. (Total for terminals 9 & 25)