Modbus
adress
Register
Data
type
Range
Default
Description
CRHB-400 N
ECOWATT
PLUS
CRVB-400 N
ECOWATT
PLUS
CRHB-450 N
ECOWATT
PLUS
CRVB-450 N
ECOWATT
PLUS
40057
Speed_prop_to_sensor 16 BITS
0 – 1
1
0: Variable inversely
proportional to speed
1: Variable proportional to
speed
40058
AI3_Filter
16 BITS
0 – 3
1
Filtration grade of AI3:
0: None
1: Low
2: Medium
3: High
40059
AI3_alarm_limit
16BITS
0 – 100
100
Limit in percentage of AI3
input to generate IAQ alarm
40060
AI3_alarm_delay
16BITS
0 – 60
10
Time (minutes) to activate
alarm once reached the limit
COP / CAV mode
40063
PI_Kp
16BITS
0 – 10000
1000
1000
1000
1000
Proportional constant for COP
mode
40064
PI_Ki
16BITS
0 – 1000
100
100
100
100
Integral constant for COP
mode
40065
KQ_FACTOR
16BITS
0 – 2000
177
181
220
224
Airflow constant to translate
pressure reading (AI2) to
airflow
40066
Sensor_config
16BITS
0 – 1
0
0
0
0
0: Internal sensor
1: AI2 external sensor
40067
Sepoint_config
16BITS
0 – 1
1
1
1
1
0: Internal selector
1: Modbus
40068
Setpoint_PI
16BITS -32000 – 32000
100
100
100
100
100: COP mode
250: CAV mode
40069
Speed_prop_to_sensor
16BITS
0 – 1
0
0
0
0
0: Variable inversely
proportional to speed
1: Variable proportional to
speed
40070
Range_COP
16BITS
0 – 2500
750
750
550
550
Pa units
40071
Range_CAV
16BITS
0 – 10000
5500
5500
6000
6000
M3/h units
MIN/MAX mode
40073
VREG_min
16BITS
0 – 1000
4000
4000
4000
4000
Speed (mV) when min active
in MIN/MAX mode
40074
VREG_max
16BITS
0 – 1000
10000
10000
10000
10000
Speed (mV) when max active
in MIN/MAX mode
Motor alarm
40079
Motor_Speed_min
16BITS
0 – 4000
300
300
300
300
Below this motor speed,
motor alarm active (rpm)
40080
Motor_Alarm_delay
16BITS
0 – 60
10
10
10
10
Time (seconds) to activate
alarm once reached the limit
Date/Hour/Schedule/Holidays
40083
TIMER_RTC_Status
16BITS
0 – 1
0
0
0
0
Weekly planner (Timer RTC)
0: Disabled
1: Enabled
40084
Setpoint_holidays
16BITS
0 – 100
100
100
100
100
% of setpoint related to
operational mode selected
40085
Year_start_holidays
16BITS
18 – 999
18
18
18
18
Year holidays starts
40086
Month_start_holidays
16BITS
0 – 12
8
8
8
8
Months holidays starts
40087
Day_start_holidays
16BITS
0 – 32
1
1
1
1
Day holidays starts
40088
Hour_start_holidays
16BITS
0 – 23
0
0
0
0
Hour holidays starts
40089
Minutes_start_holidays 16BITS
0 – 59
0
0
0
0
Minutes holidays starts
40090
Year_end_holidays
16BITS
18 – 999
18
18
18
18
Year holidays ends
40091
Month_end_holidays
16BITS
0 – 12
8
8
8
8
Months holidays ends