Element
Position
Function
S4
0
Modo MIN/MAX
1
COP / CAV mode, setpoint to 20% full scale - (factory default)
2
COP / CAV mode, setpoint to 30% full scale
3
COP / CAV mode, setpoint to 40% full scale
4
COP / CAV mode, setpoint to 50% full scale
5
COP / CAV mode, setpoint to 60% full scale
6
COP / CAV mode, setpoint to 70% full scale
7
COP / CAV mode, setpoint to 80% full scale
8
COP / CAV mode, setpoint to 90% full scale
9
COP / CAV mode, setpoint to 100% full scale
A
Proportional mode, setting A
B
Proportional mode, setting B
C
Proportional mode, setting C
D
Proportional mode, setting D
E
Proportional mode, setting E
F
Proportional mode, setting F
5.1. CONSTANT PRESSURE (COP)
Operating mode where the roof fan maintains a constant pressure setpoint within the limits of the unit performance
curve. Factory default operation mode.
For verifi cation or activation of COP operation mode:
1. Microswitch S1.1 in OFF position (see locations in section 4.2).
2. Tube marked as “P” connected to left pressure tap of the terminal box.
3. Pressure setpoint adjustment using potentiometer S4. Table below indicates the
setpoint value (Pa) according to the position and roof fan model:
S4
position
CRHB-CRVB
400 N ECOWATT
CRHB-CRVB
450 N ECOWATT
1
150 Pa
110 Pa
2
225 Pa
165 Pa
3
300 Pa
220 Pa
4
375 Pa
275 Pa
5
450 Pa
330 Pa
6
525 Pa
385 Pa
7
600 Pa
440 Pa
8
675 Pa
495 Pa
9
750 Pa
550 Pa