32
9.
MAPA MODBUS / MODBUS MAP / CARTE MODBUS
DISCRETE INPUTS
Modbus
adress
Register
Data
type
Range
Default
Description
CRHB-400 N
ECOWATT
PLUS
CRVB-400 N
ECOWATT
PLUS
CRHB-450 N
ECOWATT
PLUS
CRVB-450 N
ECOWATT
PLUS
10001
DCV_STATE
BIT
0 – 1
0 = OFF
1 = ON
10002
BOOST_STATE
BIT
0 – 1
0 = OFF
1 = ON
10003
NIGHT_STATE
BIT
0 – 1
0 = OFF
1 = ON
10004
MIN/MAX_STATE
BIT
0 – 1
0 = OFF
1 = ON
10005
AN_IN1_Definition
BIT
0 – 1
0 = 0-10V
1 = 4-20mA
10006
AN_IN2_Definition
BIT
0 – 1
0 = 0-10V
1 = 4-20mA
10007
AN_IN3_Definition
BIT
0 – 1
0 = 0-10V
1 = 4-20mA
10008
Alarm_AN1
BIT
0 – 1
IAQ sensor alarm AN1:
0 = NO ALARM
1 = ALARM
10009
Alarm_AN2
BIT
0 – 1
IAQ sensor alarm AN2:
0 = NO ALARM
1 = ALARM
10010
Alarm_AN3
BIT
0 – 1
IAQ sensor alarm AN3:
0 = NO ALARM
1 = ALARM
OUTPUT COILS
Modbus
adress
Register
Data
type
Range
Default
Description
CRHB-400 N
ECOWATT
PLUS
CRVB-400 N
ECOWATT
PLUS
CRHB-450 N
ECOWATT
PLUS
CRVB-450 N
ECOWATT
PLUS
1
ON_OFF
BIT
0 – 1
1
1
1
1
External ON/OFF relay
As default, joint from factory
2
BOOST_MODE
BIT
0 – 1
0
0
0
0
3
NIGHT_MODE
BIT
0 – 1
0
0
0
0
4
MIN_MAX
BIT
0 – 1
0
0
0
0
INPUT REGISTERS
Modbus
adress
Register
Data type
Range
Description
30001
VIN_INTERN_DISP
16 BITS
-32000 – 32000
Internal sensor value in Pa (if COP mode) or m3/h (if CAV mode)
30002
AN_IN1_PHYSICAL_VALUE
16 BITS
-32000 – 32000
Real AI1 value depending on holding registers 40033 and 40034
30003
AN_IN2_PHYSICAL_VALUE
16 BITS
-32000 – 32000
Real AI2 value depending on holding registers 40044 and 40045
30004
AN_IN3_PHYSICAL_VALUE
16 BITS
-32000 – 32000
Real AI3 value depending on holding registers 40055 and 40056
30005
AN1_VALUE
16 BITS
0 - 10000
Current value of analog output AN_IN1 (mV)
30006
AN2_VALUE
16 BITS
0 - 10000
Current value of analog output AN_IN2 (mV)
30007
AN3_VALUE
16 BITS
0 - 10000
Current value of analog output AN_IN3 (mV)
30008
SLAVE_OUTPUT_VALUE
16 BITS
0 - 10000
Current value of analog output AN_OUT (mV)
30009
MOTOR_SPEED
16 BITS
0 - 5000
Current motor speed (rpm)
30010
MOTOR_VREG
16 BITS
0 - 10000
Motor regulation voltage (mV)
Summary of Contents for ECOWATT PLUS CRHB 400 N