![S&P ECOWATT PLUS CRHB 400 N Manual Download Page 33](http://html1.mh-extra.com/html/sandp/ecowatt-plus-crhb-400-n/ecowatt-plus-crhb-400-n_manual_3222240033.webp)
33
Modbus
adress
Register
Data type
Range
Description
30011
ROTATIONAL_SWITCH_S4
16 BITS
0 - 16
0: MIN-MAX mode
1: COP or CAV mode with a 20% setpoint of the full scale
2: COP or CAV mode with a 30% setpoint of the full scale
3: COP or CAV mode with a 40% setpoint of the full scale
4: COP or CAV mode with a 50% setpoint of the full scale
5: COP or CAV mode with a 60% setpoint of the full scale
6: COP or CAV mode with a 70% setpoint of the full scale
7: COP or CAV mode with a 80% setpoint of the full scale
8: COP or CAV mode with a 90% setpoint of the full scale
9: COP or CAV mode with a 100% setpoint of the full scale
10: Proportional mode (A configuration)
11: Proportional mode (B configuration)
12: Proportional mode (C configuration)
13: Proportional mode (D configuration)
14: Proportional mode (E configuration)
15: Proportional mode (F configuration)
16: Proportional mode (G configuration)
30012
MOTOR_STATUS
16 BITS
0 – N
0: Stop
1: Running
2: Alarm (when you try to start de motor (Vreg>1,5V) and it does not
work
30014
YEAR
16 BITS
18 – 999
Current year if configured before (holding register 40095)
30015
MONTH
16 BITS
1 – 12
Current year if configured before (holding register 40096)
30016
DAY
16 BITS
1 – 31
Current year if configured before (holding register 40097)
30017
HOUR
16 BITS
0 – 23
Current year if configured before (holding register 40098)
30018
MINUTE
16 BITS
0 – 59
Current year if configured before (holding register 40099)
30019
SECOND
16 BITS
0 – 59
Current year if configured before (holding register 40100)
30021
MOTOR_ALARM_COUNT
16 BITS
0 – 65535
Motor alarm counter
30022
AN1_ALARM_COUNT
16 BITS
0 – 65535
AN1 IAQ alarm counter
30023
AN2_ALARM_COUNT
16 BITS
0 – 65535
AN2 IAQ alarm counter
30024
AN3_ALARM_COUNT
16 BITS
0 – 65535
AN3 IAQ alarm counter
30025
MINUTES_ON
16 BITS
0 – 1440
Minutes of device powered
30026
DAYS_ON
16 BITS
0 – 65535
Days of device powered
30027
MINUTES_RUNNING
16 BITS
0 – 1440
Minutes of device running
30028
DAYS_RUNNING
16 BITS
0 – 65535
Days of device running
30029
P_ALARM_1
16 BITS
0 – 1
Last motor alarm:
0: No alarm
1: Motor alarm
30030
P_YEAR_ALARM_1
16 BITS
18 – 999
Year of last motor alarm
30031
P_MONTH_ALARM_1
16 BITS
1 – 12
Month of last motor alarm
30032
P_DAY_ALARM_1
16 BITS
1 – 31
Day of last motor alarm
30033
P_HOUR_ALARM_1
16 BITS
0 – 23
Hour of last motor alarm
30034
P_MINUTES_ALARM_1
16 BITS
0 – 59
Minute of last motor alarm
30035
P_SECONDS_ALARM_1
16 BITS
0 – 59
Second of last motor alarm
30036
P_ALARM_2
16 BITS
0 – 1
Second to last motor alarm:
0: No alarm
1: Motor alarm
30037
P_YEAR_ALARM_2
16 BITS
18 – 999
Year of second to last motor alarm
30038
P_MONTH_ALARM_2
16 BITS
1 – 12
Month of second to last motor alarm
30039
P_DAY_ALARM_2
16 BITS
1 – 31
Day of second to last motor alarm
30040
P_HOUR_ALARM_2
16 BITS
0 – 23
Hour of second to last motor alarm
30041
P_MINUTES_ALARM_2
16 BITS
0 – 59
Minute of second to last motor alarm
30042
P_SECONDS_ALARM_2
16 BITS
0 – 59
Second of second to last motor alarm