S&P ECOWATT PLUS CRHB 400 N Manual Download Page 15

15

EN

Element

Terminals

Description

J12

0V, + 
(SLAVE)

0-10V regulation slave output to other equipment. By factory default, slave output will be same 
as equipment regulation speed. Parameter only modifiable through Modbus communication. 

J14

0V, D1, D0, 
12V

Modbus RS485 communication connection and +12V power supply (300mA max.)

J15

D1, D0

Modbus RS485 communication connection 

J17

-

USB connector

S1

1, 2, 3, 4

1 – OFF: Constant pressure operation (COP) - (factory default)
 

ON: Constant airflow operation (CAV)

2 – No use
3 – OFF: Hardware parameterization (selector and switches) - (factory default)
 

ON: Parameterization via Modbus

4 – No use

S2

1, 2, 3

1 – OFF: AI1 analog input, 0-10V - (factory default)
 

ON: AI1 analog input, 4-20mA

2 – OFF: AI2 analog input, 0-10V - (factory default)
 

ON: AI2 analog input, 4-20mA

3 – OFF: AI3 analog input, 0-10V - (factory default)
 

ON: AI3 analog input, 4-20mA

S3

1, 2, 3

1 – OFF: Force cannel 1 Modbus communication - (factory default)
 

ON: Modbus communication channel selected (holding register 40001)

2 – OFF: Modbus communication parameters: 19200, even, 1stop bit - (factory default)
 

ON: Communication parameters according to Modbus modification (holding registers 40002 
- 40003)

3 – OFF: Modbus network end impedance enabled - (factory default)
 

ON: Modbus network end impedance disabled

S4

-

16-position selector (0 – 9, A – F), operating modes and settings  

BT1

-

CR2032 battery. Maintains the configured time when the equipment is not powered (necessary 
in case of time schedule via Modbus) 

F1

-

Protection fuse (5x20, 6.3A, T)

D3

-

Red LED that indicates motor alarm. Constant flashing when motor alarm is activated 

D4

-

Green LED that indicates main power. Fixed when powered.  

D5

-

Green LED that indicates Modbus communication. On/Off sequence according to Modbus 
protocol.  

5. OPERATION MODES

ECOWATT PLUS units allow the following operating modes:  
• 

Constant pressure (COP) 

mode, by factory default, with modifi able setpoint parameters. 

• 

Constant airfl ow (CAV)

 mode with modifi able setpoint parameters. 

• 

Variable airfl ow volume (VAV)

 mode by installing an external sensor with 0-10V or 4-20mA analog signal.

• 

MIN/MAX

 mode.

Operating mode and setpoint setting selection are made by means of the microswitch S1.1 and the selector S4 (see 
locations in section 4.2). The microswtich is ON/OFF type and the selector has 16 positions (0 – 9, A – F). Parameters 
described below:   

Element

Position

Function

S1.1

OFF

COP operation mode - (factory default)

ON

CAV operation mode

Summary of Contents for ECOWATT PLUS CRHB 400 N

Page 1: ...CRHB CRVB 400 450 N ECOWATT PLUS ES EN FR...

Page 2: ...IENTO 5 5 1 Presi n constante COP 6 5 2 Caudal constante CAV 7 5 3 Caudal proporcional variable VAV 7 5 4 M nimo m ximo 8 6 OTRAS FUNCIONES 8 6 1 Paro marcha remoto 8 6 2 Boost 8 6 3 Noche 9 6 4 Rel a...

Page 3: ...or lo tanto se basan principalmente en el cumplimiento de las normas de car cter general Por consiguiente reco mendamos a todas las personas expuestas a riesgos que se atengan escrupulosamente a las n...

Page 4: ...n 12V Alimentaci n motor Alimentaci n equipo Conexi n Modbus Elemento Terminales Descripci n J1 L N GND Alimentaci n equipo 230V 10 50 60 Hz J2 GND L1 N1 Salida alimentaci n motor cableado de f brica...

Page 5: ...i n seg n modificaci n Modbus holding registers 40002 40003 3 OFF Impedancia final red Modbus habilitada por defecto de f brica ON Impedancia final red Modbus deshabilitada S4 Selector 16 posiciones 0...

Page 6: ...proporcional configuraci n F 5 1 PRESI N CONSTANTE COP Modo de funcionamiento donde el extractor de tejado mantiene una consigna de presi n constante dentro de los l mites de la curva caracter stica...

Page 7: ...m h 2400 m h 4 2750 m h 3000 m h 5 3300 m h 3600 m h 6 3850 m h 4200 m h 7 4400 m h 4800 m h 8 4950 m h 5400 m h 9 5500 m h 6000 m h 5 3 CAUDAL PROPORCIONAL VARIABLE VAV Modo de funcionamiento donde...

Page 8: ...A S2 2 OFF Entrada anal gica AI2 0 10V ON Entrada anal gica AI2 4 20mA S2 3 OFF Entrada anal gica AI3 0 10V ON Entrada anal gica AI3 4 20mA 5 4 M NIMO M XIMO Modo de funcionamiento donde el ventilador...

Page 9: ...vaci n 6 5 MODBUS 6 5 1 Caracter sticas b sicas Todos los equipos ECOWATT PLUS incorporan protocolo de comunicaci n Modbus RTU con una con guraci n por de fecto de f brica descrita a continuaci n Tipo...

Page 10: ...o con gurar de forma independiente cada unidad y asign ndole un n mero de canal distinto 6 6 TIMER RTC La funci n TIMER RTC est disponible en todos los equipos pero su con guraci n es nicamente a trav...

Page 11: ...os y acortar a sensiblemente la vida del mismo En todos los trabajos de mantenimiento y reparaci n deben observarse las normas de seguridad vigente en cada pa s 8 PUESTA FUERA DE SERVICIO Y RECICLAJE...

Page 12: ...1 Constant pressure COP 16 5 2 Constant air ow CAV 17 5 3 Variable ai ow volume VAV 17 5 4 Minimum maximum 18 6 OTHER FUNCTIONS 18 6 1 Remote stop start 18 6 2 Boost 18 6 3 Night 19 6 4 Alarm relay 1...

Page 13: ...commend all people exposed to hazards to strictly follow the safety regulations in force in your country S P will not be held liable for any possible harm or damage caused by non compliance with the s...

Page 14: ...y Equipment supply Modbus connection Element Terminals Description J1 L N GND Equipment supply 230V 10 50 60 Hz J2 GND L1 N1 Output motor supply factory wiring J3 ON OFF Remote Stop Start via normally...

Page 15: ...to Modbus modification holding registers 40002 40003 3 OFF Modbus network end impedance enabled factory default ON Modbus network end impedance disabled S4 16 position selector 0 9 A F operating modes...

Page 16: ...rtional mode setting E F Proportional mode setting F 5 1 CONSTANT PRESSURE COP Operating mode where the roof fan maintains a constant pressure setpoint within the limits of the unit performance curve...

Page 17: ...m h 2400 m h 4 2750 m h 3000 m h 5 3300 m h 3600 m h 6 3850 m h 4200 m h 7 4400 m h 4800 m h 8 4950 m h 5400 m h 9 5500 m h 6000 m h 5 3 VARIABLE AIFLOW VOLUME VAV Operating mode where fan performs a...

Page 18: ...S2 1 OFF AI1 analog input 0 10V ON AI1 analog input 4 20mA S2 2 OFF AI2 analog input 0 10V ON AI2 analog input 4 20mA S2 3 OFF AI3 analog input 0 10V ON AI3 analog input 4 20mA 5 4 MINIMUM MAXIMUM Ope...

Page 19: ...next activation 6 5 MODBUS 6 5 1 Basic characteristics All ECOWATT PLUS units incorporate Modbus RTU communication protocol with a factory default con guration des cribed below Tipo interface Modbus R...

Page 20: ...work it is necessary to con gure each unit independently and assign it a different channel number 6 6 TIMER RTC TIMER RTC function is available in all units but its con guration is only through Modbus...

Page 21: ...be dangerous and perceptibly shorten the working life of fan unit While cleaning great care should be taken not to unbalance blades or impeller All maintenance and repair work should be carried out i...

Page 22: ...5 1 Pression constante COP 26 5 2 D bit constant CAV 27 5 3 D bit proportionnel variable VAV 27 5 4 Minimum maximum 28 6 AUTRES FONCTIONS 28 6 1 Arr t marche distance 28 6 2 Boost 28 6 3 Nuit 29 6 4 R...

Page 23: ...la conformit avec les normes g n rales Ainsi nous conseillons vivement toutes les personnes concern es d appliquer les r gles en vigueur dans leurs pays en mati re de pr vention d accidents La respon...

Page 24: ...r e analogique 1 Raccordement Modbus et alimentation 12V Alimentation moteur Alimentation quipement Raccordament Modbus l ment Bornes Description J1 L N GND Alimentation quipement 230V 10 50 60 Hz J2...

Page 25: ...tion d apr s modification Modbus holding registers 40002 40003 3 OFF Imp dance finale r seau Modbus activ par d faut ON Imp dance de sortie de r seau Modbus d sactiv e S4 S lecteur 16 positions 0 9 A...

Page 26: ...RESSION CONSTANTE COP Dans ce mode de fonctionnement la tourelle d extraction de toiture maintient une consigne de pression constante dans les limites de la courbe caract ristique de l quipement Con g...

Page 27: ...m h 1800 m h 3 2200 m h 2400 m h 4 2750 m h 3000 m h 5 3300 m h 3600 m h 6 3850 m h 4200 m h 7 4400 m h 4800 m h 8 4950 m h 5400 m h 9 5500 m h 6000 m h 5 3 D BIT PROPORTIONNEL VARIABLE VAV Dans ce m...

Page 28: ...e AI2 0 10V ON Entr e analogique AI2 4 20mA S2 3 OFF Entr e analogique AI3 0 10V ON Entr e analogique AI3 4 20mA 5 4 MINIMUM MAXIMUM Dans ce mode de fonctionnement le ventilateur bascule entre deux vi...

Page 29: ...uis activation 6 5 MODBUS 6 5 1 Caract ristiques g n rales Tous les quipements ECOWATT PLUS int grent le protocole de communication Modbus RTU avec la con guration par d faut ci apr s Type interface M...

Page 30: ...damment et se voir attribuer un num ro de canal diff rent 6 6 PROGRAMMATION HORAIRE TIMER RTC La fonction programmation horaire est disponible sur tous les quipements mais sa con guration se fait uniq...

Page 31: ...it sensiblement la dur e de vie de l appareil Dans les op rations de nettoyage faites attention ne pas d s quilibrer l h lice ou la roue Dans tous les travaux de maintenance et r paration veuillez obs...

Page 32: ...FF BIT 0 1 1 1 1 1 External ON OFF relay As default joint from factory 2 BOOST_MODE BIT 0 1 0 0 0 0 3 NIGHT_MODE BIT 0 1 0 0 0 0 4 MIN_MAX BIT 0 1 0 0 0 0 INPUT REGISTERS Modbus adress Register Data t...

Page 33: ...ar if configured before holding register 40099 30019 SECOND 16 BITS 0 59 Current year if configured before holding register 40100 30021 MOTOR_ALARM_COUNT 16 BITS 0 65535 Motor alarm counter 30022 AN1_...

Page 34: ...t IAQ alarm 30056 S_SECONDS_ALARM_2 16 BITS 0 59 Second of second to last IAQ alarm HOLDING REGISTERS Modbus adress Register Data type Range Default Description CRHB 400 N ECOWATT PLUS CRVB 400 N ECOW...

Page 35: ...OST_Active_State 16 BITS 0 1 0 0 0 0 BOOST 0 Normally open NO 1 Normally close NC 40024 MIN MAX_Active_State 16 BITS 0 1 0 0 0 0 MIN MAX 0 Normally open NO 1 Normally close NC Operation modes 40027 OP...

Page 36: ...input AI2 40045 AI2_Sensor_out_max 16 BITS 32000 32000 2000 Equivalent physical units when 10v 40mA of analog input AI2 40046 Speed_prop_to_sensor 16 BITS 0 1 1 0 Variable inversely proportional to s...

Page 37: ...iable inversely proportional to speed 1 Variable proportional to speed 40070 Range_COP 16BITS 0 2500 750 750 550 550 Pa units 40071 Range_CAV 16BITS 0 10000 5500 5500 6000 6000 M3 h units MIN MAX mode...

Page 38: ...999 Year configuration 40096 Current_month 16BITS 1 12 Month configuration 40097 Current_day 16BITS 1 31 Day configuration 40098 Current_hour 16BITS 0 23 Hour configuration 40099 Current_minute 16BIT...

Page 39: ...39...

Page 40: ...S P SISTEMAS DE VENTILACI N S L U C Llevant 4 Pol gono Industrial Llevant 08150 Parets del Vall s Barcelona Espa a Tel 34 93 571 93 00 www solerpalau com Ref 9023105000...

Reviews: