Modbus
adress
Register
Data
type
Range
Default
Description
CRHB-400 N
ECOWATT
PLUS
CRVB-400 N
ECOWATT
PLUS
CRHB-450 N
ECOWATT
PLUS
CRVB-450 N
ECOWATT
PLUS
40036
AI1_Filter
16 BITS
0 – 3
1
Filtration grade of AI1
0: None
1: Low
2: Medium
3: High
40037
AI1_alarm_limit
16BITS
0 – 100
100
Limit in percentage of AI1
input to generate IAQ alarm
40038
AI1_alarm_delay
16BITS
0 – 60
10
Time (minutes) to activate
alarm once reached the limit
40041
AI2_CONFIG
16 BITS
0 – 4
0
Analog input AI2
configuration:
0: Disable
1: Humidity sensor
2: Temperature
3: CO2/VOC (ppm)
4: 0-10V/4-20mA (another
parameters)
40042
SETPOINT_prop_AI2
16 BITS -32000 – 32000
0
Setpoint VAV mode. Units
depending input configuration
40043
AI2_Band
16 BITS -32000 – 32000
Humidity: 40
Temperature: 10
CO2/VOC: 1000
0-10/4-20: 10% of scale
Band VAV mode
40044
AI2_Sensor_out_min
16 BITS -32000 – 32000
0
Equivalent physical units
when 0v/4mA of analog input
AI2
40045
AI2_Sensor_out_max
16 BITS -32000 – 32000
2000
Equivalent physical units
when 10v/40mA of analog
input AI2
40046
Speed_prop_to_sensor 16 BITS
0 – 1
1
0: Variable inversely
proportional to speed
1: Variable proportional to
speed
40047
AI2_Filter
16 BITS
0 – 3
1
Filtration grade of AI2:
0: None
1: Low
2: Medium
3: High
40048
AI2_alarm_limit
16BITS
0 – 100
100
Limit in percentage of AI2
input to generate IAQ alarm
40049
AI2_alarm_delay
16BITS
0 – 60
10
Time (minutes) to activate
alarm once reached the limit
40052
AI3_CONFIG
16 BITS
0 – 4
0
Analog input AI3
configuration:
0: Disable
1: Humidity sensor
2: Temperature
3: CO2/VOC (ppm)
4: 0-10V/4-20mA (another
parameters)
40053
SETPOINT_prop_AI3
16 BITS -32000 – 32000
0
Setpoint VAV mode. Units
depending input configuration
40054
AI3_Band
16 BITS -32000 – 32000
Humidity: 40
Temperature: 10
CO2/VOC: 1000
0-10/4-20: 10% of scale
Band VAV mode
40055
AI3_Sensor_out_min
16 BITS -32000 – 32000
0
Equivalent physical units
when 0v/4mA of analog input
AI3
40056
AI3_Sensor_out_max
16 BITS -32000 – 32000
2000
Equivalent physical units
when 10v/40mA of analog
input AI3