Appendix A Outdoor GPS Antenna Installation
Verizon 4G LTE Network Extender 2 for Enterprise User Guide v1.0
110
Copyright © 2019, All Rights Reserved.
Grounding the Optional GPS Arrestor
The way to connect the ground cable with the GPS arrestor is as follows.
Table 33. Grounding the GPS Arrestor (MGB GPS Arrestor)
Classification
Description
Installation section
MGB ground terminal of arrestor
Cable
AWG8, F-GV 6 mm2 × 1C/1 EA
Heat shrink tube
(spec/color/length)
Ф 0.4 in. (10 mm)/Green/1.97 in. (50 mm)
Pressure terminal
MGB
Checking the MGB specifications per site and preparing
fasteners
Arrestor
6 mm2, ring type, hole dia.: 0.21 in. (5.3 mm)
Fastener
MGB
Checking the MGB specifications per site and preparing
fasteners
Arrestor
M5 hex. bolt/1 EA
M5 spring washer/1 EA
M5 plane washer/1 EA
(attached at the GPS arrestor)
Recommended torque
value (kgf.cm)
M5 hex. bolt
1.45~2.17 ft.lb. (20 ~ 30 kgf.cm)
Working tools
Cable cutter, wire stripper, compressor, heating gun, torque driver (+), torque
wrench, and nipper
Pressure Terminal for Grounding
As for the pressure terminal or the cable, the UL listed products or equivalent
should be used.
For example:
Manufacturer: JEONO Electric
GPS Arrestor: 6 mm2 Pressure Terminal (JOR 6-5)